Specified Controls SC-Z20 Installation Manual Download Page 15

SC-Z20

WIRING DETAILS

GENERAL NOTES

I

nstall the SC-Z20 control panel on a flat surface near the HVAC equipment. The panel should be installed in a dry, clean

location approximately 60 inches from the floor. Do not install the control panel on or inside a rooftop unit.

24 VOLT POWER

The control panel requires a 24 Volt transformer with a proper VA rating. Do not power the control panel from the
transformer in the HVAC equipment. Connect 24 Volts to the terminals labeled

on the interface

24 VAC INPUT POWER

board. 18-2 thermostat wire is recommended.

DISCHARGE AIR TEMPERATURE SENSOR

The control panel requires a discharge air temperature sensor. Mount the sensor 26 inches from the HVAC equipment in
the supply duct. Connect the sensor to the terminals labeled

on the interface board. 18-2 thermostat wire is

DAS

recommended.

HVAC UNIT

The control panel is wired to the HVAC equipment in the same way as a standard 2-stage heat / 2-stage cool thermostat.
Connect the HVAC equipment to the terminals labeled

on the interface board. 18-8 thermostat wire is

HVAC SYSTEM

recommended.

R, C, Y, AND W ZONE DAMPER TERMINALS

The control panel requires a heating and cooling contact closure from each zone damper. Connect terminals

,

, , and

R C Y

W

R C, Y

W

from each zone damper to the terminals labeled

,

, and

on the interface board. 18-4 thermostat wire is

recommended.

SC-Z20-NS PROGRAMMABLE NIGHT STAT (OPTIONAL)

The control panel has an optional input for a SC-Z20-NS programmable night stat. To install the thermostat, remove the
factory installed jumper between the two terminals labeled

and

and wire the jumper across terminals

and . Refer to

T

T

R

T

the SC-Z20-NS wiring and programming instructions in this manual.

MINIMUM CALLS SELECTION SWITCHES

The control panel is equipped with two

selector switches located on the interface board. When both

Minimum Calls

switches are in the OFF position, any zone calling can bring on the equipment. When the

switch is in the ON

2 ZONES

position, at least two zones have to call to bring on the equipment. When the

switch is in the ON position, at least

3 ZONES

three zones have to call to bring on the equipment. If both

and

switches are in the ON position, the

2 ZONES

3 ZONES

default is three.

TIME DELAY SPEED UP BUTTON

The control panel is equipped with a time delay speed up button. When the speed up button is engaged the time delays
between stages and between modes of operation are divided by 15. The time delay speed up mode will reset after fifteen
minutes. Time delay speed up should only be used for start up and service.

Summary of Contents for SC-Z20

Page 1: ...SC Z20 Commercial Zone Control System Modulating or Two position Installation Manual...

Page 2: ...Works with single stage multi stage or heat pump systems No programming required Auxiliary heat control option for each zone Night setback option All low voltage wiring LEDs indicates status of equipm...

Page 3: ...second stage The system will remain in whatever mode it is in for a minimum of fifteen minutes If equal heating and cooling calls take place cooling will receive priority Equipment mode of operation i...

Page 4: ...SC Z20 MODULATING ZONE CONTROL SYSTEM WIRING AND LAYOUT GUIDE 3 SC Z20 NS NIGHT STAT SC Z20...

Page 5: ...OOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE STATUS HEAT COOL DAS ACTIVE OCCUPI...

Page 6: ...on Zones 1 20 RED Heat ON when there is a call for heating GREEN Cool ON when there is a call for cooling HVAC System W1 GREEN ON when first stage heat is energized W2 GREEN ON when second stage heat...

Page 7: ...T COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE TIME DELAYS DIVIDED BY 15 STATU...

Page 8: ...AT Insert a small flat bladed screw driver in the release slot located on the bottom of the thermostat and pry straight up and away from the subbase Avoid twisting the case as this may stress the LCD...

Page 9: ...rge air temperature at the damper is below 72 degrees the zone damper will open on a call for cooling SC Z20 PANEL NOTES Use standard 18 gauge thermostat wire Run four wire cable from the panel termin...

Page 10: ...S DS HEAT COOL WIRE TO OPTIONAL SLAVE DAMPER UP TO 20 MAY BE WIRED IN PARALLEL SC Z20 T AUTO CHANGEOVER SPACE THERMOSTAT FACTORY JUMPER RED LED INDICATES A CALL FOR HEATING GREEN LED INDICATES A CALL...

Page 11: ...t T terminals on the SC Z20 panel that places the system in the occupied or unoccupied mode of operation The thermostat can also be used with a SC T32 S1 Indoor Remote Sensor 24 volt power to the ther...

Page 12: ...HE CLOCK AND DAY OF WEEK It is important that the time of day and day of the week is set properly so that occupied and unoccupied programs start on time 1 Touch the until the day of the week flashes T...

Page 13: ...ram to additional days of the Program CPY week use the or arrow to add additional days Example UP DOWN Mon Tue Wed Thu Fri 13 Once you have selected the days to be copied touch will begin to flash and...

Page 14: ...hat the HVAC equipment have two stages of heating and two stages of cooling The pressure drop through the zone dampers is negligible and should not be a factor when sizing branch duct runs Zone damper...

Page 15: ...e from each zone damper Connect terminals and R C Y W R C Y W from each zone damper to the terminals labeled and on the interface board 18 4 thermostat wire is recommended SC Z20 NS PROGRAMMABLE NIGHT...

Page 16: ...discharge air setpoint If the number of zones calling for heating and cooling are equal the system will operate in the cooling mode first This is known as Cooling Priority Each zone damper or diffuse...

Page 17: ...ol shall be required for setup and not troubleshooting B The zone control panel shall be suitable for the indoor ambient Environment conditions and shall be rated for operation between 32 F and 120 F...

Page 18: ...nected to the output shaft 2 All actuators shall be factory wired to the damper control board 3 All damper actuators shall be mounted outside of the air stream B The damper actuator control board shal...

Page 19: ...ermostat wire 18 gauge minimum No shielded cable shall be required 3 Control wire and cable shall be installed in accordance with NEC 1 06 SERVICE AND GUARANTEE A The entire zone control system shall...