Specified Controls SC-Z20 Installation Manual Download Page 10

SYSTEM NOTES:

Use standard 18 gauge thermostat wire.

Actuator requires a 24VAC 40VA transformer.

Option 2: Sensor can be relocated after the electric duct heater. RY1 relay coil can be wired to terminals

Option 1: RY1 can be used to bring on electric heat and drive damper open without relocating sensor. A 15K Ohm

PO
PC

W
R
C

DS
DS

Y

1
2
3
4
5
6
7
8
C
R
R
Y
W

1

2
3
4
5

ACTUATOR

BOARD

DAMPER OR

DIFFUSER

ACTUATOR

90 SECOND TIMING
90° STROKE

44 lb.-

in.

2

VA

DAMPER OPEN

(24VAC)

DAMPER CLOSED

(24VAC)

CALL FOR HEAT

(24VAC)

24VAC POWER

(HOT)

24VAC POWER

(COM.)

DUCT SENSOR
DUCT SENSOR

CALL FOR COOL

(24VAC)

DUCT SENSOR

(10K OHMS @77°)

OPEN

CLOSED

COM.

DS

DS

HEAT

COOL

WIRE TO

OPTIONAL

SLAVE

DAMPER

(UP TO 20 MAY BE WIRED

IN PARALLEL)

SC-Z20-T

AUTO CHANGEOVER

SPACE THERMOSTAT

FACTORY JUMPER

RED LED

INDICATES

A CALL FOR

HEATING

GREEN LED

INDICATES

A CALL FOR

COOLING

OPTION 1

resistor must be wired to the relay contacts so that when the relay is energized, the resistor will be in parallel with
the duct sensor. This will change the ohms value translating to a higher duct temperature which will drive the damper
open.

NC  C   NO

RY1

RELAY

24 V

COIL

15K Ohm Resistor

SC-Z20-T MODULATING OR TWO-POSITION

ZONE THERMOSTAT

WIRE TO SC-Z20

ZONE PANEL TERMINALS

3 and 5 on the actuator board. Relay contacts are wired in series with the duct heater coil.

OPTION 2

NC  C   NO

RY1

RELAY

24 V

COIL

WIRE TO DUCT HEATER COIL

5   3

WIRING DIAGRAM FOR ZONE HAVING AN ELECTRIC DUCT HEATER

COM

OPEN

CLOSE

Summary of Contents for SC-Z20

Page 1: ...SC Z20 Commercial Zone Control System Modulating or Two position Installation Manual...

Page 2: ...Works with single stage multi stage or heat pump systems No programming required Auxiliary heat control option for each zone Night setback option All low voltage wiring LEDs indicates status of equipm...

Page 3: ...second stage The system will remain in whatever mode it is in for a minimum of fifteen minutes If equal heating and cooling calls take place cooling will receive priority Equipment mode of operation i...

Page 4: ...SC Z20 MODULATING ZONE CONTROL SYSTEM WIRING AND LAYOUT GUIDE 3 SC Z20 NS NIGHT STAT SC Z20...

Page 5: ...OOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE STATUS HEAT COOL DAS ACTIVE OCCUPI...

Page 6: ...on Zones 1 20 RED Heat ON when there is a call for heating GREEN Cool ON when there is a call for cooling HVAC System W1 GREEN ON when first stage heat is energized W2 GREEN ON when second stage heat...

Page 7: ...T COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE TIME DELAYS DIVIDED BY 15 STATU...

Page 8: ...AT Insert a small flat bladed screw driver in the release slot located on the bottom of the thermostat and pry straight up and away from the subbase Avoid twisting the case as this may stress the LCD...

Page 9: ...rge air temperature at the damper is below 72 degrees the zone damper will open on a call for cooling SC Z20 PANEL NOTES Use standard 18 gauge thermostat wire Run four wire cable from the panel termin...

Page 10: ...S DS HEAT COOL WIRE TO OPTIONAL SLAVE DAMPER UP TO 20 MAY BE WIRED IN PARALLEL SC Z20 T AUTO CHANGEOVER SPACE THERMOSTAT FACTORY JUMPER RED LED INDICATES A CALL FOR HEATING GREEN LED INDICATES A CALL...

Page 11: ...t T terminals on the SC Z20 panel that places the system in the occupied or unoccupied mode of operation The thermostat can also be used with a SC T32 S1 Indoor Remote Sensor 24 volt power to the ther...

Page 12: ...HE CLOCK AND DAY OF WEEK It is important that the time of day and day of the week is set properly so that occupied and unoccupied programs start on time 1 Touch the until the day of the week flashes T...

Page 13: ...ram to additional days of the Program CPY week use the or arrow to add additional days Example UP DOWN Mon Tue Wed Thu Fri 13 Once you have selected the days to be copied touch will begin to flash and...

Page 14: ...hat the HVAC equipment have two stages of heating and two stages of cooling The pressure drop through the zone dampers is negligible and should not be a factor when sizing branch duct runs Zone damper...

Page 15: ...e from each zone damper Connect terminals and R C Y W R C Y W from each zone damper to the terminals labeled and on the interface board 18 4 thermostat wire is recommended SC Z20 NS PROGRAMMABLE NIGHT...

Page 16: ...discharge air setpoint If the number of zones calling for heating and cooling are equal the system will operate in the cooling mode first This is known as Cooling Priority Each zone damper or diffuse...

Page 17: ...ol shall be required for setup and not troubleshooting B The zone control panel shall be suitable for the indoor ambient Environment conditions and shall be rated for operation between 32 F and 120 F...

Page 18: ...nected to the output shaft 2 All actuators shall be factory wired to the damper control board 3 All damper actuators shall be mounted outside of the air stream B The damper actuator control board shal...

Page 19: ...ermostat wire 18 gauge minimum No shielded cable shall be required 3 Control wire and cable shall be installed in accordance with NEC 1 06 SERVICE AND GUARANTEE A The entire zone control system shall...

Reviews: