SC-Z20-NS PROGRAMMING INSTRUCTIONS

HOW IT WORKS:

The SC-Z20-NS does not control the HVAC equipment and only uses the ‘G’ fan relay to put the SC-Z20 panel in either the
occupied or unoccupied mode. This is accomplished by using the Programmable Fan option so that the fan relay is energized
during occupied mode (Always On) and de-energized during unoccupied mode (Automatic). When in Automatic mode, the fan
relay will only energize when the temperature rises above or falls below the programmed unoccupied heating and cooling
setpoints.

RECOMMENDED SETUP:

Refer to the Installation Instructions to configure the thermostat. Leave all other setup menu items not shown below in factory
default.

SYSTEM SWITCH SETTINGS:

The SC-Z20-NS contains a set of four system switches located on the thermostat printed circuit board. Make sure the system
switches are set as follows:

Sw 1 = OFF
Sw 2 = ON
Sw 3 = OFF
Sw 4 = OFF

INSTALLER SETUP MENU CHANGES:

After the thermostat is powered up, touch and hold both the

and

section for 5 second to enter the Installer Menu.

Clock

Mode

Touch

to advance forward through the menu or touch

to backup.

Mode

Fan

MENU CHANGES: (LEAVE ALL OTHER OPTIONS AT FACTORY DEFAULTS)

02 = 2

(2 schedules per day)

04 = 1

(Programmable Fan)

After the above changes have been made, touch and hold

until the thermostat exits the Installer Setup menu.

Mode

SETTING THE CLOCK AND DAY OF WEEK:

It is important that the time of day and day of the week is set properly so that occupied and unoccupied programs start on time.

1. Touch the

until the day of the week flashes. Tap the

or

arrow to select the day of the week.

Clock

UP

DOWN

2. Touch

again and the hour will flash. Tap the

or

arrow to select the correct hour. Note: PM hours are indicated

Clock

UP

DOWN

by

on the LCD.

PM

3. Touch

again and the minutes will flash. Tap the

or

arrow to select the correct minutes.

Clock

UP

Down

4. To exit the menu, touch

again.

Clock

DAYLIGHT SAVING TIME:

Refer to the User Manual and DST Chart for Daylight Saving Time option.

PROGRAMMING EVENTS:

When the thermostat is configured to provide 2 schedules per day (Occupied/Unoccupied), 7 day per week, each event is
displayed on the LCD as

(Occupied) and

(Unoccupied).

DAY

NIGHT

1. Touch

until

(Monday) flashes.

Program

Mon

2. Tap

again until the hour flashes and

is displayed on the LCD. Use the

or

arrow to set the hour start

Program

Day

UP

DOWN

time. Note: PM hours are indicated by

on the LCD.

PM

3. Tap

again until the minutes flash. Use the

or

arrow to set the minutes.

Program

UP

DOWN

4. Tap

again and the heating setpoint will flash. Leave the setpoint at the factory default of 70 degrees.

Program

5. Tap

again and the cooling setpoint will flash. Leave the setpoint at the factory default of 75 degrees.

Program

6. Tap

again and the fan option

will flash. This is the correct setting for the Day mode. If not, use the

or

Program

Always On

UP

DOWN

arrow to set the fan option from Automatic to Always On.

Summary of Contents for SC-Z20

Page 1: ...SC Z20 Commercial Zone Control System Modulating or Two position Installation Manual...

Page 2: ...Works with single stage multi stage or heat pump systems No programming required Auxiliary heat control option for each zone Night setback option All low voltage wiring LEDs indicates status of equipm...

Page 3: ...second stage The system will remain in whatever mode it is in for a minimum of fifteen minutes If equal heating and cooling calls take place cooling will receive priority Equipment mode of operation i...

Page 4: ...SC Z20 MODULATING ZONE CONTROL SYSTEM WIRING AND LAYOUT GUIDE 3 SC Z20 NS NIGHT STAT SC Z20...

Page 5: ...OOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE STATUS HEAT COOL DAS ACTIVE OCCUPI...

Page 6: ...on Zones 1 20 RED Heat ON when there is a call for heating GREEN Cool ON when there is a call for cooling HVAC System W1 GREEN ON when first stage heat is energized W2 GREEN ON when second stage heat...

Page 7: ...T COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE TIME DELAYS DIVIDED BY 15 STATU...

Page 8: ...AT Insert a small flat bladed screw driver in the release slot located on the bottom of the thermostat and pry straight up and away from the subbase Avoid twisting the case as this may stress the LCD...

Page 9: ...rge air temperature at the damper is below 72 degrees the zone damper will open on a call for cooling SC Z20 PANEL NOTES Use standard 18 gauge thermostat wire Run four wire cable from the panel termin...

Page 10: ...S DS HEAT COOL WIRE TO OPTIONAL SLAVE DAMPER UP TO 20 MAY BE WIRED IN PARALLEL SC Z20 T AUTO CHANGEOVER SPACE THERMOSTAT FACTORY JUMPER RED LED INDICATES A CALL FOR HEATING GREEN LED INDICATES A CALL...

Page 11: ...t T terminals on the SC Z20 panel that places the system in the occupied or unoccupied mode of operation The thermostat can also be used with a SC T32 S1 Indoor Remote Sensor 24 volt power to the ther...

Page 12: ...HE CLOCK AND DAY OF WEEK It is important that the time of day and day of the week is set properly so that occupied and unoccupied programs start on time 1 Touch the until the day of the week flashes T...

Page 13: ...ram to additional days of the Program CPY week use the or arrow to add additional days Example UP DOWN Mon Tue Wed Thu Fri 13 Once you have selected the days to be copied touch will begin to flash and...

Page 14: ...hat the HVAC equipment have two stages of heating and two stages of cooling The pressure drop through the zone dampers is negligible and should not be a factor when sizing branch duct runs Zone damper...

Page 15: ...e from each zone damper Connect terminals and R C Y W R C Y W from each zone damper to the terminals labeled and on the interface board 18 4 thermostat wire is recommended SC Z20 NS PROGRAMMABLE NIGHT...

Page 16: ...discharge air setpoint If the number of zones calling for heating and cooling are equal the system will operate in the cooling mode first This is known as Cooling Priority Each zone damper or diffuse...

Page 17: ...ol shall be required for setup and not troubleshooting B The zone control panel shall be suitable for the indoor ambient Environment conditions and shall be rated for operation between 32 F and 120 F...

Page 18: ...nected to the output shaft 2 All actuators shall be factory wired to the damper control board 3 All damper actuators shall be mounted outside of the air stream B The damper actuator control board shal...

Page 19: ...ermostat wire 18 gauge minimum No shielded cable shall be required 3 Control wire and cable shall be installed in accordance with NEC 1 06 SERVICE AND GUARANTEE A The entire zone control system shall...

Reviews: