8. GENERAL INSTALLATION INSTRUC-
TIONS FOR INSTALLATION SPACES
MADE FROM COMBUSTIBLE CON-
STRUCTION MATERIALS
8.1 FLOORS, ATTACHMENT WALLS AND CEILING
22
23
19
24
21
15
16
23
11
12
14
17
13
18
20
8
The fireplace cladding must
be suitable for heat dissipation
(active surfaces or convection air
openings)!
The figure shows the installation situation using the Varia 1V-51-4S with convection air housing as an
example
and applies as an example for all fireplace inserts.
8 Insulation of the heating chamber using, e.g., dimensionally stable mineral wool according to the heat
insulation thickness technical data.
11 Supply air grille (hot are outlet) The position must be selected in such a manner,that
a distance of 500 mm is between the top edge of the grille and the ceiling.
12 Heating chamber
13 Chimney cladding made from non-combustible construction material
14 Mounting frame with insulation strips
15 Separate combustion air connection
16 Air circulation grille (cold air supply)
17 Insulated flue gas pipe (connecting piece) with at least 3 cm thick dimensionally stable mineral wool
18 Insulation of the connecting lines with at least 3 cm thick dimensionally stable mineral wool
19 Convection air housing made of steel plate
20 Top insulation of the convection air housing min. 3 cm
21 Observe the air return!
22 Combustible construction material (wooden floor)
23 Stud wall, 10 cm thick*
24 Floor protection covering within the heating chamber made from non-combustible material as long as
no insulation is necessary according to the heat insulation thickness of the technical data!
* If necessary, use a substitute insulation material (e.g. calcium silicate) in the place of front-mounted
masonry and insulation (point 8), in accordance with the technical data provided by the manufacturer.