background image

Page 7

Page 6

For the most efficient & quiet operation:

•  ALWAYS, when possible, reduce the number or transitions and turns. If long duct run is required, increase 

duct size from 8” to 10” or bigger size duct. If a reducer is used, install a long reducer instead of a pancake 

reducer. Reducing duct size will restrict airflow and decrease airflow, thus reduce duct size as far away from 

opening as possible. 

•  Use no more than three 90° elbows.

•  Make sure there is a minimum of 24” (61 cm) of straight vent between the elbows if more than one elbow is used.

•  DO NOT install two elbows together.

•  The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.

•  The vent system must have a damper. If roof or wall cap has a damper, DO NOT use damper (if supplied) on top of the 

range hood.

•  Use silver tape or duct tape to seal all joints in the vent system.

•  Use caulking to seal exterior wall or roof opening around the cap. 

Please use 

Duct Run Calculation

 below to com

-

pute total available duct run when using elbows, transitions and caps.

•  If turns or transitions are required: Install as far away from opening and as far apart, between 2, as possible.

•  If available, also refer to stove top manufacturer’s height clearance requirements and recommended hood 

mounting height above range.

* Due to different ceiling height configurations, recommended height may not be applicable.

Minimum Duct Size:

•  Round - 8” minimum

•  Rectangular - 3-1/4 x 10” minimum (requires a provided 3-1/4x10” adaptor)

Duct Run Calculation:

Recommended maximum run

8” or 3-1/4 x 10” duct

50 ft

Vent piece deduction

Each 90º elbow used

9 ft

Each 45º elbow used

5 ft

Each 8” to 3/14 x 10” transition used

7 ft

Side wall cap with damper

0 ft

Roof cap

0 ft

Duct Run Calcuation example:

One roof cap, two 90º elbow, and one 45º elbow used:
0ft + 9ft + 9ft + 5ft = 23ft used.
Deduct 23ft from 50ft, 27ft maximum available for 

straight duct run.

Calculating Vent System Length

To calculate the length of the system you need, deduct the equivalent feet for each vent piece used in the system 

from the recommended maximum duct run.

Venting Requirements

Venting Methods

•  This range hood is factory set for venting through the roof or wall.

•  Vent work can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.

IMPORTANT:

•  NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling, attics or        

garages. All exhaust must be ducted to the outside.

•  Use metal/aluminum duct work only. 

•  Fasten all connections with sheet metal screws and tape all joints with certified Silver Tape or Duct Tape.

•  Use caulking to seal exterior wall or roof opening around the cap.

Vertical roof venting

Roof cap

Option 2:

Side wall cap

Horizontal wall venting

Option 1:

Summary of Contents for PS19

Page 1: ...nual Professional Built in hood Professional Insert Liners IMPORTANT Read and save these instructions NOTICE Installer Leave this guide with the homeowner Homeowner Keep this guide for future reference Rev 2036u 1c Spagna Vetro PS19 ...

Page 2: ...rities Before servicing or cleaning unit switch power OFF at service panel and lock service panel to pre vent power from being switched ON accidentally Clean grease laden surfaces frequently To reduce the risk of fire and to disperse air properly make sure to vent air outside DO NOT vent exhaust into spaces between walls crawl spaces ceiling attics or garages Ducted fans MUST always be vented to t...

Page 3: ...er and or distributor reseller further declines all responsibility for injury due to neg ligence and the warranty of the unit automatically expires due to improper maintenance The manufacturer and or distributor reseller will not be held responsible for any damages to per sonal property or real estate or any bodily injuries whether caused directly or indirectly by the range hood Clean ventilating ...

Page 4: ...tant to install the hood at the proper mounting height Hoods mounted too low could result in heat damage and fire hazard while hoods mounted too high will be hard to reach and will loose its performance and efficiency It is recommended that the range hood be vented vertically through the roof through 8 20 3 cm or bigger round metal aluminum vent work Always use rigid type metal aluminum ducts if a...

Page 5: ...d mounting height above range Due to different ceiling height configurations recommended height may not be applicable Minimum Duct Size Round 8 minimum Rectangular 3 1 4 x 10 minimum requires a provided 3 1 4x10 adaptor Duct Run Calculation Recommended maximum run 8 or 3 1 4 x 10 duct 50 ft Vent piece deduction Each 90º elbow used 9 ft Each 45º elbow used 5 ft Each 8 to 3 14 x 10 transition used 7...

Page 6: ...Valley Road Cleveland Ohio 44131 5575 Advanced Preparations 1 Be familiar with the controls of the range hood by reading through Range Hood Operations Page 12 2 Place the range hood on a flat stable surface Connect the range hood to a designated standard outlet please refer the product label for the suitable voltage of this unit and turn on the range hood Verify all operations of the range hood by...

Page 7: ...al shock this range hood must be properly grounded Make sure this is done by qualified electrician in accordance with all applicable national and local electrical codes Before connecting wires switch power off at service panel and lock service panel to prevent power from being switched on accidentally 7 Connect the range hood to a designated standard outlet or cut off the plug and connect three wi...

Page 8: ...hood before cooking and allow it to operate several minutes after the cooking is completed to clear all smoke and odors from the kitchen Button functions Power Power ON OFF the range hood and activate power off delay timer Decrease Value Blower motor speed decrease timer value decrease and enter timer mode Increase Value Blower motor speed increase timer value increase and cleaning reminder reset ...

Page 9: ...arette ashes ignitable substances or any foreign objects into blowers NEVER leave cooking unattended When frying oil in the pan can easily overheat and catch fire The risk of self combustion is higher when the oil has been used several times NEVER cook on open flames under the range hood Check deep fryers during use Superheated oil may be flammable Cleaning The saturation of greasy residue in the ...

Page 10: ...ted from millimeters thus inch measurements are estimated Professional Insert Liner Wiring Diagram 4 Speed NOTE Wiring Diagrams shown above with GU10 light configuration A transformer is required for MR16 Lights Wiring Diagram 6 Speed Measurements Wiring Diagram Continued Measurements Wiring Diagram ...

Page 11: ...You must present proof of original purchase date Please provide an original dated proof of purchase sales receipt invoice in order to obtain service under warranty The information in this document is subject to change without notice please contact your local reseller for updated details Warranty SAFETY WARNING Never put your hand into area housing the fan while the fan is operating For optimal ope...

Page 12: ... A restocking fee of 15 will be charged for all approved return s Exchanges or returns may not be accepted if any packaging is missing Make sure to inspect the hood for damages and defects before installation Appearance flaws of the hood found after installation and not affecting hood performance is not covered under our warranty for returns or exchang es Service visits not covered under warranty ...

Page 13: ...Spagna Vetro Appliances Inc Burnaby BC Canada www KitchenHoods ca tel 604 430 5252 SPAGNA VETRO ...

Reviews: