– 44 –
ILAHP Inverter Extreme Air-to-Water Heat Pump
Address Function Number
Content
mode
Default Description
Remark
1086
03/16
F21
Timer mute
read/write
0
0-no/1-yes
DIGI1
1087
03/16
F22
Manual-control Fan Speed
read/write
0
0-no/1-yes
DIGI1
1088
03/16
Reserved
read/write
1089
03/16
F23
DC fan rated speed
read/write
600r
300~1300
DIGI1
1090
03/16
REserved
read/write
1101
03/16
Reserved
read/write
1102
03/16
Reserved
read/write
1103
03/16
F25
Cooling fan max speed
read/write
700r
300~1300
DIGI1
1104
03/16
F26
Heating fan max speed
read/write
700r
300~1300
DIGI1
1105
03/16
Reserved
read/write
1106
03/16
Reserved
read/write
1107
03/16
Reserved
read/write
1108
03/16
Reserved
read/write
1109
03/16
Reserved
read/write
1110
03/16
D01
Start defrosting setpoint
read/write
-7°C
-30~5.0°C
TEMP1
1111
03/16
Reserved
read/write
1112
03/16
D02
Exit defrosting setpoint
read/write
13°C
0.0~30.0°C
TEMP1
1113
03/16
D03
Defrosting cycle
read/write
45min
30~90Min
DIGI1
1114
03/16
D04
Max defrosting time
read/write
8min
1~12 Min
DIGI1
1115
03/16
Reserved
read/write
1116
03/16
D07
Electric heater control
read/write
0
0-no/1-yes
DIGI1
1117
03/16
D08
Sliding defrost ambient temp
read/write
2°C
-30~10.0°C
TEMP1
1118
03/16
D09
Sliding defrost:ambient temp difference
read/write
14°C
1~50.0°C
TEMP1
1119
03/16
D10
Sliding defrost:coil temp difference
read/write
10°C
1~50.0°C
TEMP1
1120
03/16
Reserved
read/write
1121
03/16
D11
Sliding defrost:min coil temp
read/write
-30°C
-30.0~50.0°C
TEMP1
1122
03/16
Reserved
read/write
1123
03/16
D12
Defrosting compressor frequency
read/write
70
30~90Hz
DIGI1
1124
03/16
Reserved
read/write
1125
03/16
Reserved
read/write
1126
03/16
Reserved
read/write
1127
03/16
Reserved
read/write
1128
03/16
Reserved
read/write
1129
03/16
Reserved
read/write
1130
03/16
Reserved
read/write
1131
03/16
E01
EEV1 EEV adjust mode
read/write
1
0-Manual/1-Auto
DIGI1
1132
03/16
E02
EEV1 target superheat
read/write
5
-20.0~20.0°C
TEMP1
1133
03/16
E03
EEV1 EEV initial steps
read/write
350
0~500N
DIGI1
1134
03/16
Reserved
read/write
1135
03/16
Reserved
read/write
1136
03/16
Reserved
read/write
1137
03/16
E07
EEV min Steps
read/write
100
0~500N
DIGI1
1138
03/16
E08
Cooling initialSteps
read/write
200
0~500N
DIGI1
1139
03/16
E09
EVI1:adjustment mode
read/write
1
0-Manual/1-Auto
DIGI1
1140
03/16
E10
EVI1:initial steps
read/write
350
0~500N
DIGI1
1141
03/16
Reserved
read/write
1142
03/16
Reserved
read/write
1143
03/16
E13
EVI target superheat
read/write
3
-20.0~20.0°C
TEMP1
1144
03/16
E14
EVI:min steps
read/write
100
0~500N
DIGI1
1145
03/16
Reserved
read/write
1146
03/16
Reserved
read/write
1147
03/16
E17
Defrost steps
read/write
480
10~500N
DIGI1
1148
03/16
E18
Target superheat for cooling
read/write
3
-20.0~20.0°C
TEMP1
1149
03/16
Reserved
read/write
1150
03/16
Reserved
read/write
1151
03/16
Reserved
read/write
1152
03/16
G01
Sterilize target temp
read/write
63
60~70°C
TEMP1
1153
03/16
G02
Sterilize maintain time
read/write
0
0~60min
DIGI1
1154
03/16
G03
Sterilize start time
read/write
1
0~23h
DIGI1
1155
03/16
G04
Sterilize cycle
read/write
30
1~30days
DIGI1
1156
03/16
G05
Sterilize function
read/write
1
0-no/1-yes
DIGI1
1157
03/16
R01
Hot water target temp
read/write
55
R36-R37
TEMP1