
– 42 –
ILAHP Inverter Extreme Air-to-Water Heat Pump
1. Transmission Format
Baud Rate
9600bps
Start bit
1
Byte width
8
Parity
N
Stop bits
1
Slave address
H15
2. Packet Format
Address
Function
Data
CRC checksum
16bits
16bits
03:Function of reading multi registers
16:Function of presenting multi registers
06: Fuction of presenting single
N*16bits
16bits
Address Function Number
Content
mode
Default Description
Remark
1011
03/16
ON/OFF
read/write
0-OFF/1-ON
DIGI1
1012
03/16
Mode
read/write
H05=1:0-Hot water/1-Heating/2-Cooling/3-Hot
water+heating/4-Hot water+Cooling
H05=0:0-Hot water/1-Heating/3-Hot water+heating
DIGI1
1013
03/16
Reserved
read/write
1014
03/16
Reserved
read/write
1015
03/16
Reserved
read/write
1016
03/16
Manual control
read/write
bit0:Manual defrost(0-off 1-on)
bit1:Mute flag bit (0-off 1-on)
bit2:A key manual heating (0-off 1-on)
DIGI1
1017
03/16
Reserved
read/write
1018
03/16
H01
if with disable automatic restart (0-no/1-
yes)
read/write
1
0-no/1-yes
DIGI1
1019
03/16
Reserved
read/write
1020
03/16
Reserved
read/write
1021
03/16
H05
Cooling Mode
read/write
1
0-No/1-Yes
DIGI1
1022
03/16
Reserved
read/write
1023
03/16
H07
Controler choice
read/write
0
0-display control 1-remote control
DIGI1
1024
03/16
H10
Unit address
read/write
1
1~32
DIGI1
1025
03/16
Reserved
read/write
1026
03/16
Reserved
read/write
1027
03/16
H27
EVI enabled
read/write
3
0-no EVI
1-EVI on cooling
2-EVI on heating
3-EVI both heating and cooling
DIGI1
1028
03/16
H28
Hot water mode enable
read/write
1
0-no/1-yes
DIGI1
1029
03/16
H21
Temperature unit
read/write
0
0-°C/1-F
DIGI1
1030
03/16
H22
Silence mode
read/write
1
0-no/1-yes
DIGI1
1031
03/16
Reserved
read/write
Data Types Description
TEMP
Important Note: All temperatures values in the MODBUS registers are stored as tenths of a degree Celsius, regardless of whether the unit is set to
display Fahrenheit or Celsius.
Therefore, a temperature value such as register 1192 = Heating Target Temperature may be stored as 500. Divide this value by 10 and you get
50.0°C. To determine the equivalent value in Fahrenheit, multiply this value by 9/5, to get 90, then add 32. The Fahrenheit temperature is 122°F.
Therefore, a temperature value such as register 1192 = Heating Target Temperature may be stored as 500. Divide this value by 10 and you get
50.0°C. To determine the equivalent value in Fahrenheit, multiply this value by 9/5, to get 90, then add 32. The Fahrenheit temperature is 122°F.
When a value represents a difference between two temperatures, such as register 1194, Start temperature differential, the conversion from Celsius to
Fahrenheit is simply, multiply by 9/5, and from Fahrenheit to Celsius is multiply by 5/9.
For example, if the default value is 36, divide this by 10 and it represents 3.6 deg Celsius difference, multiply by 9/5 to get 6.5 deg Fahrenheit
difference. Conversely, if you want to set this value to 5 deg Fahrenheit differential, multiply by 5/9 to get 2.8 deg Celsius differential. Divide this by
10, and set the register value to 28.
DIGI1
No symble byte,unit :1,When show 123,the data transmission is 123;
DIGI2
No symble byte,unit :10,When show 1230,the data transmission is 123;
DIGI3
No symble byte,unit :100,When show 12300,the data transmission is 123;
DIGI4
No symble byte,unit :5,When show 10,the data transmission is 2;
DIGI5
No symble byte,unit :0.1,When show 12.3,the data transmission is 123;
DIGI6
No symble byte,unit :0.001,When show 0.123,the data transmission is 123;
DIGI9
No symble byte,unit :0.01,When show 0.12,the data transmission is 12;
3. Data types
Modbus RTU Protocol
4. Mailing Address