– 43 –
ILAHP Inverter Extreme Air-to-Water Heat Pump
Address Function Number
Content
mode
Default Description
Remark
1032
03/16
H18
Electric heater energy stage
read/write
3
1-Electric heater stage 1
2-Electric heater stage 2
3-Electric heater stage 3
DIGI1
1033
03/16
H20
3-way valve polarity
read/write
0
0-ON on hot water mode/1-OFF on hot water mode
DIGI1
1034
03/16
H29
Model running parameter code
read/write
0
0~20
DIGI1
1035
03/16
H25
Control temp chioce when heat/cool
mode
read/write
0
0-outlet water temp./1-room temp.
DIGI1
1036
03/16
H30
Hydraulic module enable
read/write
0
0-no,1-yes
DIGI1
1037
03/16
A03
Heat pump shutdown ambient temp
read/write
-25°C
-40.0~10.0°C
TEMP1
1038
03/16
A04
Antifreeze setting temp
read/write
4°C
A22~10.0°C
TEMP1
1039
03/16
A05
Antifreeze setting temp difference
read/write
3°C
1.0~50.0°C
TEMP1
1040
03/16
A06
Exhaust temp protect setting
read/write
120°C
60.0~130.0°C
TEMP1
1041
03/16
H31
Water pump type
read/write
0
0-not water flow function
1- Grundfos 25-75
2- Grundfos 25-105
3- Grundfos 25-125
1042
03/16
A11
low pressure sensor enable
read/write
0
0-no,1-yes
DIGI1
1043
03/16
Reserved
read/write
1044
03/16
Reserved
read/write
1045
03/16
H32
Force running time of DHW change to
heating
read/write
120
1~180min
DIGI1
1046
03/16
Reserved
read/write
1047
03/16
Reserved
read/write
1048
03/16
Reserved
read/write
1049
03/16
Reserved
read/write
1050
03/16
Reserved
read/write
1051
03/16
Reserved
read/write
1052
03/16
A21
Ambient/Suction/Coil Sensor type
read/write
0
0-5K/1-2K
DIGI1
1053
03/16
A22
Antifreeze min temp setting
read/write
4°C
-20°C~10°C
TEMP1
1054
03/16
Reserved
read/write
1055
03/16
Reserved
read/write
1056
03/16
Reserved
read/write
1057
03/16
Reserved
read/write
1058
03/16
Reserved
read/write
1059
03/16
F01
Fan motor type
read/write
3
1-Double speed motor/3-DC fan motor
DIGI1
1060
03/16
F02
Coil temp setting when fan high speed on
cool mode
read/write
50°C
-15.0~60.0°C
TEMP1
1061
03/16
Reserved
read/write
1062
03/16
F03
Coil temp setting when fan low speed on
cool mode
read/write
10°C
-15.0~60.0°C
TEMP1
1063
03/16
Reserved
read/write
1064
03/16
Reserved
read/write
1065
03/16
Reserved
read/write
1066
03/16
F05
Coil temp setting when fan high speed on
heat mode
read/write
10°C
-15.0~60.0°C
TEMP1
1067
03/16
Reserved
read/write
1068
03/16
F06
Coil temp setting when fan low speed on
heat mode
read/write
20°C
-15.0~60.0°C
TEMP1
1069
03/16
Reserved
read/write
1070
03/16
Reserved
read/write
1071
03/16
Reserved
read/write
1072
03/16
Reserved
read/write
1073
03/16
Reserved
read/write
1074
03/16
F10
Fan quantity
read/write
0
0-single/1-double
DIGI1
1075
03/16
Reserved
read/write
1076
03/16
Reserved
read/write
1077
03/16
Reserved
read/write
1078
03/16
Reserved
read/write
1079
03/16
Reserved
read/write
1080
03/16
Reserved
read/write
1081
03/16
F18
Fan motor min Speed in cooling
read/write
300r
300~1300
DIGI1
1082
03/16
Reserved
read/write
1083
03/16
F19
Fan motor min Speed in Heating
read/write
300r
300~1300
DIGI1
1084
03/16
Reserved
read/write
1085
03/16
Reserved
read/write