– 36 –
ILAHP Inverter Extreme Air-to-Water Heat Pump
Top Menu Number
Name
Range
Factory
Default
Description
Pump
P01
Running Mode
Ordinary/Special/
Interval
Special
R01 = Ordinary, Pump runs whenever Remote On/Off is closed.
R01 = Special, Pump runs when when Remote On/Off and Heat/
Cool On/Off is closed. R01 = Interval, Pump runs on intervals
according to P02 and P03
P02
Running Interval Time
1-120
30
Interval between Main Circulator runs when R02 = 2
P03
Running Duration
1-30
3
Run time of Main Circulator when R01 = 2
P04
Advanced Start Time
N/A
N/A
Not used on this unit.
P05
Domestic Hot Water Pump Working Mode
Ordinary/Special/
Interval
Special
R05 = Ordinary, DHW Pump runs whenever DHW On/Off is closed.
R05 = Special, Pump runs when whenDHW On/Off is closed and
TT is below DHW setpoint - R32. R05 = Interval, Pump runs on
intervals according to P02 and P03
Disinfection
G01
Setpoint
140-158°F
145
Target temperature or Sterilize cycle
G02
Time of Duration
0-60
30
Duration of Sterilize Cycle
G03
Start Time
0-23
23
Time of day (24h) to start Sterilize cycle. 23 = 11:00 PM
G04
Work Cycle
1-30
7
Number of days between Sterilize cycles
G05
High Temp Disinfection
Yes/No
No
G05 =No, Sterilize Cycle is Dormant G05 =Yes, Sterilize Cycle is
active
Compressor
C01
Manual Frequency
0-120
0
This fixes the compressor at a fixed speed, in Hz. If C01 = 0,
compressor speed will modulate
C02
Minimum Frequency
20-60
30
The minimum speed, in Hz, that the compressor will modulate to in
response to the load
C03
Max Frequency
30-120
90
The maximum speed, in Hz, that the compressor will modulate to in
response to the load
C04
Model Selection
0-99
0
C04 = 0 for all ILAHP. Do not Change
C05
Minimum Frequency of Low Ambient Temp
(Cooling)
0-60
50
The minimum speed, in Hz, that the compressor will modulate to in
response to the load when the Ambient temperature is below 23°F
C06
Frequency Control Mode
1-120
1
C06 = 1 for all ILAHP. Do not change
C07
Resonance Point 1
N/A
N/A
Not used on this unit.
C08
Resonance Point 2
N/A
N/A
Not used on this unit.
C09
Resonance Point 3
N/A
N/A
Not used on this unit.