Page 6 of 24
3.1.6
Minimum clearance from combustibles.
Fig. 2
MODEL
HORIZONTAL
45
0
ABOVE
BELOW
SIDE
FRONT
BACK
FRONT
BACK
SRP08
610mm
610mm
865mm
205mm
915mm
1220mm
610mm
SRP15
915mm
915mm
1830mm
305mm
915mm
2590mm
1145mm
SRP22
1145mm
1145mm
2085mm
305mm
915mm
2975mm
1270mm
SRP30 -DEEP
1375mm
1375mm
2365mm
305mm
915mm
3355mm
1525mm
SRP30 - PARABOLIC
1880mm
1880mm
3025mm
305mm
915mm
4270mm
1905mm
3.2
Gas Supply
3.2.1
Natural Gas - G20 at 20mbar supply pressure (appliance cat 2H).
Maximum supply pressure (Pmax)-
25mbar
Minimum supply pressure (Pmin) -
17mbar
Setting Pressure
-
12.5mbar
Gas Connection
-
Rc - ½
3.2.1.1 Installation pipes should be fitted in accordance with National and Local Regulations. Pipes of a smaller size
than the appliance connection (Rc - ½) should not be used and the pipework must be designed to achieve a
gas supply pressure between the maximum and minimum valves stated above, measured at the appliance inlet
pressure test point.
A union service cock MUST be fitted as close as practicable upstream of the appliance to enable
the gas train to be removed for maintenance or repair.
It is essential to provide a flexible metallic hose, which must conform to National or Local
Regulations, to connect the appliance to the gas supply. Minimum size to be ½" (12.7mm) bore.
45° max
Above
Below
Below
Side
Side
Back
Front
Back
Front
Above
Above