UN-PACKING
The appliance is supplied in a carton, assembled complete and ready for installation. Any optional equipment
supplied is packed inside the carton also.
3
INSTALLATION
Not withstanding their limited scope, the appliance should be installed in accordance with the relevant
provisions of any National Gas Safety (Installation and Use Regulations). Will account should also be taken of
any obligations arising from any National Health and Safety at Work Regulations, National and Local Building
Regulations and National Electrical Wiring Regulations. The appliance must be installed, and where necessary,
converted for use on other gases, by a qualified installer.
3.1
Suspension
3.1.1
The appliance should be located with respect to building construction and other equipment, to permit access to
the appliance for servicing etc.
3.1.2
For suspending the appliance, it is recommended that suitable protected welded chain (ø3mm x 65 links/m) or
ø6mm (minimum) mild steel drop rods and suitable brackets are used. Attach the chains or drop rods to the 4
holes located at each corner of the appliance plenum body, by use of M8 screws and nuts. Providing at least
ø5mm closed link hooks are used, chains may be attached directly to the 4 holes in the appliance plenum body.
3.1.3
The appliance must be suspended with its longitudinal axis horizontal, but may have its lateral axis either
horizontal or at an angle of up to 45
0
(maximum) from the horizontal, as shown in Fig. 1. below.
IMPORTANT:
When suspended at an angle from the horizontal, the appliance MUST be positioned with the
exhaust vent (located between the plenum body and reflector) along the higher side of the appliance.
3.1.4
The appliance may be mounted off a vertical surface also in which case it is recommended that use is made of
the purpose designed pair of brackets that are available as optional equipment. The brackets provide for a
range of mounting angles from the horizontal (15
0
, 22.5
0
, 30
0
, 37.5
0
, 45
0
) by virtue of adjustable straps attached
to the surface mounted brackets.
3.1.5
The brackets should first be fixed to the vertical surface by means of 4 bolts (M8 minimum) through pre-formed
holes in the brackets. Attach the brackets to the 4 holes located at each corner of the appliance plenum body
by use of M8 screws and nuts.
Fig. 1
45° max
Adjustable
Wall Brackets
15°/22.5°/30°/37.5°/45°
Exhaust Vent
Exhaust Vent
Exhaust Vent
2°