Form #42710000
-16-
May 2013
INTERNAL CONNECTION WIRING DIAGRAM
INTERNAL CONNECTION WIRING DIAGRAM
INTERNAL CONNECTION WIRING DIAGRAM
INTERNAL CONNECTION WIRING DIAGRAM —
—
—
—
Direct Spark Ignition
Direct Spark Ignition
Direct Spark Ignition
Direct Spark Ignition
WIRE LEGEND
ENGLISH
FRANCAIS
BK
BLACK
NOIR
W
WHITE
BLANC
R
RED
ROUGE
BL
BLUE
BLEU
G
GREEN
VERT
V
VIOLET
VIOLET
A
AMBER
AMBRE
42706000 Rev. J 1/2012
BL
BL
BK
BK
R
W
BK
BK
R
BK
W
BK
BK
BK
W
DRAFT
INDUCER
MOTOR
GAS VALVE
AIR SWITCH
TRANSFORMER
120V PRIMARY
24V SECONDARY
A
G
R
HIGH VOLTAGE
CABLE
ELECTRODE
GAP 3/16
CONTINUE TO
ADDITIONAL
HEATERS
NEUTRAL
120V
THERMOST
A
T
GROUND
L1
L2
TERMINAL
BLOCK
FACTORY WIRING
FIELD WIRING
CONNECTION WIRING DIAGRAM
CONTROL CABINET
If any of the original wire as supplied
with the appliance must be replaced.
It must be replaced with wiring material
having a temperature rating of at least
105oC. (18 AWG. - UL / CSA 600V
Type TEW)
When connecting the supply circuit to
the heater, wiring material having a
minimum size of 14 AWG and a
temperature rating of at least 90oC
shall be used.
MONITORING LIGHTS
Schéma de circuit de connexion
Circuit d'origine
Connexions client
Lampes témoins
Neutre
Terre
Vers les autres
radiateurs
Plaque à
bornes
Transformateur
bobine primaire 120ÊV
bobine secondaire 24ÊV
pressostat
Robinet à gaz
Écartement
d'électrode
4,7Êmm
Haute tension
Armoire de commande
Moteur
d'amorce
d'aspiration
S'il faut remplacer un fil de l'appareil
d'origine, utiliser exclusivement des fils
à température de service nominale
d'au moins 105C (18 AWG. - UL / CSA
600ÊV
Type TEW).
Pour raccorder le circuit d'alimentation
au radiateur, utiliser des fils de calibre
14 AWG ou plus à température de
service nominale d'au moins 90C.
FUSE 2A
G
IGNITION MODULE
GND
(BURNER)
25V
Bloc d'allumage
VALVE
VALVE
NOTES:
NOTES:
NOTES:
NOTES:
1.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring
material having a temperature rating of at least 105ºC. (18 Ga. CSA 600V Type TEW)
2.
When connecting the supply circuit to the heater, wiring material having a minimum size of 14 AWG and a
temperature rating of at least 90ºC shall be used.
3.
A replaceable 2-amp fuse (1-1/4” long) is located inside the control box.
SC
SC
SC
SCHEMATIC
HEMATIC
HEMATIC
HEMATIC WIRING DIAGRAM
WIRING DIAGRAM
WIRING DIAGRAM
WIRING DIAGRAM —
—
—
—
Direct Spark Ignition
Direct Spark Ignition
Direct Spark Ignition
Direct Spark Ignition
SCHEMATIC WIRING DIAGRAM
MOT
Motor
Moteur
GL
Green Light
Témoin vert
TRANS 24V Transformer
Transformateur 24ÊV
RL
Red Light
Témoin rouge
AS
Air Switch
pressostat
SM
Ignition Module
Bloc d'allumage
IG/S
Ignitor / Sensor
électrode
V
Gas Valve
Robinet à gaz
AL
Amber Light
Témoin ambre
MOT
120V
GL
TRANS
RL
AS
IG/S
AL
V
SM
42785000 Rev. C 10/04
25V GND
25V