Form #44201117
-34-
Dec 2021
Fig. 27
13.1
Type A
2
:
Outside (ducted) combustion air supply. When installed in a dusty or polluted atmosphere, the heater
should be fitted with a ducted supply of clean fresh air. A length of 100mm flexible ducting should be
installed between the Control Box Air Inlet and any rigid ducting and be secured to the Air Inlet with hose
clips.
Where outside combustion air is ducted directly to the burner(s) the low level natural ventilation openings
shall be not less than 50
of the areas given in Section 13 above.
13.2
Type C
12 +
C
32
:
When installing external flue single duct systems with ducted combustion air supply the distance between
the flue terminal and fresh air intake shall be no less than 1 m for both vertical and horizontal systems
13.3
Type C
52
:
When fresh air for combustion and the flue outlet are from different pressures zones as shown in figure 27,
the flue outlet and the fresh air intake must not be on surfaces that are 180 degrees apart. The acceptable
configurations are those shown in figure 27 in combination with the maximum lengths listed on table 13.
Summary of Contents for LRDL15
Page 10: ...Form 44201117 Dec 2021 9 7 0 DIMENSIONS LINEAR TUBE CONFIGURATIONS Fig 5...
Page 11: ...Form 44201117 10 Dec 2021 Fig 5a LRDL30 35 40 45 with OPTIONAL 3m EXTENSION...
Page 12: ...Form 44201117 Dec 2021 11 7 1 HEATER ASSEMBLY OVERVIEW LINEAR TUBE CONFIGURATIONS Fig 6...
Page 13: ...Form 44201117 12 Dec 2021 Fig 6a...
Page 14: ...Form 44201117 Dec 2021 13 Fig 7...
Page 15: ...Form 44201117 14 Dec 2021 Fig 7a...
Page 16: ...Form 44201117 Dec 2021 15 Fig 8...
Page 17: ...Form 44201117 16 Dec 2021 Fig 8a...
Page 39: ...Form 44201117 38 Dec 2021 16 0 TROUBLESHOOTING GUIDE...
Page 40: ...Form 44201117 Dec 2021 39...