Form
483S
Rev
Jan
09
Page 4 of 53
Table 3
MODEL
CBU15/SRL15-N
CBU15/SRL15-L
Heat Input
15. kW Hs 13.5 kW Hi
Appliance Type
A2, B
22,
C
52
Appliance Category
II
2H3+
Adjusted for
2H G20 20mbar
3+ G30/G31 29/37mbar
Setting Pressure
12.5mbar
None
Injector
No. 31
Ø1.9mm
Pre-injector
None
None
Electrical Supply
230V~50Hz 125W
Fuse Externally
3A
Dimensions
CBU 15 3.10m x 0.465m
SRL 15 5.493m x 0.34m
Weight
CBU 15 31kg
SRL 15 27kg
Gas Connection
R - ½
Flue Size
Ø100mm
Table 4
MODEL
SRU25/SRL25/ERU25-N
SRU25/SRL25/ERU25-L
Heat Input
23.0 kW Hs 20.7 kW Hi
Appliance Type (
II
2H3+
)
A2,
B
22,
C
52
Appliance Category
II
2H3+
Adjusted for
2H G20 20mbar
3+ G30/G31 29/37mbar
Appliance Type (
II
2H3P
)
A2, B
22,
C
12,
C
32,
C
52
Appliance Category
II
2H3P
Adjusted for
2H G20 20mbar
3P G31 37mbar
Setting Pressure
12.5mbar
None
Injector
Ø3.8mm
Ø2.3mm
Pre-injector
None
None
Electrical Supply
230V~50Hz 125W
Fuse Externally
3A
Dimensions
SRU25/ERU25: 5.385m x 0.465m
SRL25: 10.065m x 0.34m
Weight
SRU25: 47kg ERU25: 47kg
SRL25: 46kg
Gas Connection
R - ½
Flue Size
Ø100mm