Form
483S
Rev
Jan
09
Page 6 of 53
Table 7
MODEL
SRU40/SRL40-N
SRU40/SRL40-L
Heat Input
42.2kW Hs 38.0kW Hi
Appliance Type (
II
2H3+
)
A2,
B
22,
C
52
Appliance Category
II
2H3+
Adjusted for
2H G20 20mbar
3+ G30/G31 29/37mbar
Appliance Type (
II
2H3P
)
A2, B
22,
C
12,
C
32,
C
52
Appliance Category
II
2H3P
Adjusted for
2H G20 20mbar
3P G31 37mbar
Setting Pressure
12.5mbar
None
Injector
ø5.0mm
ø3.2mm
Pre-injector
None
None
Electrical Supply
230V~50Hz 125W
Fuse Externally
3A
Dimensions
SRU40: 6.97m x 0.715m
SRL40: 13.00m x 0.34m
Weight
SRU40: 81kg
SRL40: 79kg
Gas Connection
R - ½
Flue Size
Ø100mm
Table 8
MODEL
SRU45/SRL45-N
SRU45/SRL45-L
Heat Input
47.0 Kw Hs 42.3 Kw Hi
Appliance Type (
II
2H3+
)
A2,
B
22,
C
52
Appliance Category
II
2H3+
Adjusted for
2H G20 20mbar
3+ G30/G31 29/37mbar
Appliance Type (
II
2H3P
)
A2, B
22,
C
12,
C
32,
C
52
Appliance Category
II
2H3P
Adjusted for
2H G20 20mbar
3P G31 37mbar
Setting Pressure
12.5mbar
None
Injector
ø5.4mm
ø3.3mm
Pre-injector
None
None
Electrical Supply
230V~50Hz 125W
Fuse Externally
3A
Dimensions
SRU45: 6.97m x 0.715m
SRL45: 13.00m x 0.34m
Weight
SRU45: 81kg
SRL45: 79kg
Gas Connection
R - ½
Flue Size
Ø100mm