Southwire MaintenancePRO 23070T Operating Instructions Manual Download Page 2

Introduction

1

The Southwire 23070T MaintenancePRO

 1000A TrueRMS AC/DC 

Clamp Meter measures AC and DC current up to 1000A and offers a 

CAT IV 600V/CAT III 1000V safety rating. Other functions include AC 

and DC Voltage, Resistance, Continuity, Capacitance, Frequency, 

Duty Cycle, Temperature, and Diode Test. A built-in non-contact AC 

voltage detector and flashlight provide added convenience. This 

meter is fully tested and calibrated and, with proper use, will provide 

many years of reliable service. 

WARNINGS

• Read, understand and follow Safety Rules and Operating Instructions

  in this manual before using this meter.

• The meter’s safety features may not protect the user if not used

  in accordance to the manufacturer’s instructions. 

• Ensure that the test leads are fully seated in the input jacks and keep    

  fingers away from the metal probe tips when taking measurements.

• Before changing functions using the selector switch, always

  disconnect the test leads from the circuit under test.

• Use only UL listed test leads with the proper safety category rating.  

• Comply with all safety codes. Use approved personal protective  

  equipment when working near live electrical circuits - particularly

  with regard to arc-flash potential.

• Use caution when working on or near bare conductors or bus bars. 

• Use caution on live circuits. Voltages above 30 V AC RMS,

  42 V AC peak, or 60 V DC pose a shock hazard.

• Do not use meter or test leads if they appear damaged.

• Do not use the meter in wet or damp environments or

  during electrical storms.

• Do not use the meter near explosive vapors, dust or gasses.

• Do not use the meter if it operates incorrectly.

  Protection may be compromised. 

• Do not operate meter while Low Battery warning is on.

  Replace the battery immediately.

• Verify meter’s operation by measuring known voltage. 

• Do not apply voltage or current that exceeds the meter’s

  maximum rated input limits.

Input Limits

Function 

 Maximum Input

Amperage AC/DC 
Voltage AC/DC
Frequency, Duty Cycle,

Resistance, Diode Test,

Continuity, Capacitance 
Temperature (°C/°F)

1000A AC/DC
1000V AC/DC
600V AC/DC

600V AC/DC

2

Insulated Tip On

Insulated Tip Removed

WARNING: 

                                   Operation of meter and test leads is limited to CAT II 1000V when the insulated tip is

removed from the test probes. 

Test Leads

General Specifications

Clamp jaw opening

Diode Test

Continuity Test 

Low Battery Indication

Display 

Over Range Indication

Measurement Rate

Input Impedance

Operating Temperature

Storage Temperature

Operating Humidity

Storage Humidity

Operating Altitude

Battery

Auto Power Off

Dimensions/Weight

Safety

1.9” (48mm)
Test current of 1.5mA typical;

Open circuit voltage < 3.2V DC typical
Threshold <50

Ω

 ±5

Ω

, Test current <0.35mA

       is displayed
6000 count backlit LCD
“OL” is displayed
3 readings per second, nominal
10M

Ω

 (VAC and VDC)

41° to 104°F (5° to 40°C)
-4° to 140°F (-20° to 60°C)
Max 80% up to 87°F (31°C) decreasing linearly

to 50% at 104°F (40°C)
<80%
7000ft (2000 meters) maximum
One 9V Battery
After approx. 30 minutes
9” x 3” x 1.6” (230 x 76 x 40mm) / 0.69lb (315g)
Complies with UL 61010-1 3rd edition for measurement

CAT IV 600V, CAT lll 1000V, Pollution Degree 2

CAT IV  600V

CAT III 1000V  

CAT II

1000V

Summary of Contents for MaintenancePRO 23070T

Page 1: ...uthwiretools com 1 855 SW T00LS Toll Free Technical Help Línea de Ayuda Técnica Gratuita Scan for warranty information and to access our mobile site Escanea para informaciónde garantía y acceso a nuestro sitio móvil UL61010 1 Operating Instructions 23070T MaintenancePRO 1000A TrueRMS AC DC Clamp Meter Instrucciones de Uso Pinza Amperimétrica 23070T MaintenancePRO 1000A TrueRMS AC DC ...

Page 2: ...et or damp environments or during electrical storms Do not use the meter near explosive vapors dust or gasses Do not use the meter if it operates incorrectly Protection may be compromised Do not operate meter while Low Battery warning is on Replace the battery immediately Verify meter s operation by measuring known voltage Do not apply voltage or current that exceeds the meter s maximum rated inpu...

Page 3: ...ay not cause harmful interference and 2 This device must accept any interference received including interference that can cause undesired operation FCC Digital Emissions Compliance This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Page 4: ...on 12 LCD display 13 COM input jack 14 V Hz F C input jack 15 Non contact voltage detector 6 Symbols Used on LCD Display V A Ω F Hz F C n µ m k M OL AUTO HOLD MAX MIN REL Volts Amperes Alternating current Direct current Minus sign Ohms Continuity Diode test Farads capacitance Hertz frequency Percent duty ratio Degrees Fahrenheit Degrees Celsius nano 10 9 micro 10 6 milli 10 3 kilo 103 mega 106 Ove...

Page 5: ... Cycle when the meter is set to AC Voltage or AC Current NOTE The meter does not Autorange when the Relative mode is active The display will read OL if the difference exceeds the range 8 Operation cont Hz button The Hz button is used to select Frequency Hz or Duty Cycle when the meter is set to AC voltage AC current or Frequency Flashlight button Located on right side 4 Press the button to turn th...

Page 6: ... closed before taking a measurement For best results keep the conductor centered inside the jaw 5 Read the current on the LCD display Incorrect Correct NO YES 600A 1000A MODE REL AC DC TRMS CLAMP METER AUTO POWER OFF MAX MIN 23070T Non Contact Voltage Detector CAT IV 600V CAT III 1000V 10 1 Set the rotary function switch to the V position 2 Insert the black test lead into the COM input jack and th...

Page 7: ...he test lead probes to the component under test If the component is installed in a circuit it is best to disconnect one side before testing to eliminate interference from other devices 5 Read the resistance on the LCD display Resistance Measurements Never test resistance on a live circuit WARNING 12 Diode Test Never test diodes in a live circuit WARNING Operation cont Red Black Black Red Probe Pro...

Page 8: ...00V 14 Temperature Measurements Operation cont 1 Set the rotary function switch to the F C position 2 Press the MODE button to select readings in F or C 3 Connect the Temperature Probe to the Banana Plug Adapter Note the and markings on the adapter Connect the adapter to the meter making sure the side goes into the COM input jack and the side goes into the F C input jack 4 Touch the tip of the Tem...

Page 9: ...ranges are specified from 5 to 100 of range 10mA 0 1A 1A 2 5 8 digits 2 5 8 digits 3 0 3 digits AC Current Function Range Resolution Accuracy of reading digits 60 00A 600 0A 1000A Maximum Input 1000A DC or 1000A rms 10mA 0 1A 1A 2 5 8 digits 2 5 8 digits 3 0 3 digits DC Current Function Range Resolution Accuracy of reading digits 6 000V 60 00V 600 0V 1000V Input Protection 1000V AC rms or 1000V DC...

Page 10: ...utoranging Function Range Resolution Accuracy of reading digits 18 Specifications cont 10Hz to 10kHz 20 to 80 Input Protection 1000V AC rms or 1000V DC Duty Cycle Sensitivity 10Hz to 1kHz Sensitivity 15V AC rms 1 0 5 digits 1 5 10 digits Frequency Autoranging Duty Cycle Function Range Accuracy of reading digits Frequency through test leads when meter is set to AC voltage 40Hz to 1kHz 20 to 80 1 0 5...

Page 11: ...roduct Whether Southwire repairs or replaces the product will be a determination that Southwire makes at its sole discretion SOUTHWIRE MAKES NO WARRANTY THAT THE PRODUCT WILL BE MERCHANTABLE OR FIT FOR ANY PARTICULAR PURPOSE SOUTHWIRE MAKES NO OTHER WARRANTY EXPRESSED OR IMPLIED OTHER THAN THE WARRANTY SPECIFICALLY SET FORTH HEREIN SOUTHWIRE WILL NOT BE LIABLE FOR ANY INCIDENTAL CONSEQUENTIAL INDI...

Page 12: ...star dañados No utilice el probador en ambientes húmedos o mojados o durante tormentas eléctricas No utilice el probador cerca de vapores explosivos polvo o gases No utilice el medidor si funciona incorrectamente La protección puede verse comprometida No utilice el metro mientras que la advertencia de batería baja está encendida Reemplace la batería inmediatamente Verifique el funcionamiento del me...

Page 13: ...ción está sujeta a las dos condiciones siguientes 1 Este dispositivo no puede causar interferencias perjudiciales y 2 Este dispositivo debe aceptar cualquier interferencia recibida incluida la interferencia que pueda causar un funcionamiento no deseado Cumplimiento de las Emisiones Digitales con FCC Este equipo ha sido probado y cumple con los límites para un dispositivo digital de Clase B de acue...

Page 14: ...rada 15 Detector de voltaje sin contacto 1 2 7 10 12 13 9 15 4 6 5 8 11 14 3 Símbolos Utilizados en la Pantalla LCD 6 V A F Hz F C n µ m k M OL AUTO HOLD MAX MIN REL Voltios Amperios Corriente Alterna Corriente Continua Signo de Menos Ohmios Continuidad Prueba de Diodos Faradios capacitancia Hertz frecuencia Porcentaje proporción de funcionamiento Grados Fahrenheit Grados Celsius nano 10 9 micro 1...

Page 15: ... 30 segundos cuando el medidor se enciende inicialmente NOTA El medidor no hace el Rango Automático cuando el modo Relativo está activo En la pantalla aparecerá OL si la diferencia supera el rango 8 Operación Botón Hz El botón HZ se utiliza para seleccionar la Frecuencia Hz o el Ciclo de Trabajo cuando el metro está en voltaje AC corriente AC o Frecuencia Botón de la Linterna Ubicado en el lado de...

Page 16: ...conecte los cables de prueba y la sonda de temperatura del medidor antes de hacer mediciones de corriente con la pinza No mida corriente en conductores que estén a más de 600V sobre la tierra si está en una aplicación de CAT IV o más de1000V sobre tierra física si está en una aplicación CAT lll Observe las precauciones de seguridad al trabajar en conductores activos 10 1 Set the rotary function sw...

Page 17: ...onente se instala en un circuito es mejor desconectar un lado antes de la prueba para eliminar la interferencia de otros dispositivos 5 Lea la resistencia en la pantalla LCD Mediciones de Resistencia Nunca pruebe la resistencia en un circuito activo ADVERTENCIA Operación cont Nunca pruebe la continuidad en un circuito activo ADVERTENCIA 12 Prueba de Diodo Prueba Delantera Prueba Inversa 1 Coloque ...

Page 18: ...ltajes activos ADVERTENCIA 14 Mediciones de Temperatura 1 Coloque el interruptor de función rotativa en la posición F C 2 Pulse el botón MODE para seleccionar lecturas en F o C 3 Conecte la Sonda de Temperatura al Adaptador tipo Banana Tenga en cuenta las marcas y en el adaptador Conecte el adaptador al metro asegurándose de que el lado entre en la toma de entrada COM y el lado entre en la toma de...

Page 19: ...ima 1000A DC o 1000A rms 10mA 0 1A 1A 2 5 8 dígitos 2 5 8 dígitos 3 0 3 dígitos Corriente DC 6 000V 60 00V 600 0V 1000V Protección de Entrada 1000V AC rms o 1000V DC Ancho de banda de voltaje AC 50 a 60Hz respuesta True RMS Toda el Voltaje AC actual se especifica desde 5 a 100 del rango 1mV 10mV 0 1V 1V 1 5 5 dígitos 1 5 5 dígitos 1 5 5 dígitos 3 0 8 dígitos Voltaje AC Rango Automático 600 0mV 6 0...

Page 20: ...ión Precisión de lectura dígitos 18 10Hz a 10kHz 20 a 80 Protección de Entrada 1000V AC rms o 1000V DC Sensibilidad del Ciclo de Trabajo 10Hz a 1kHz Sensibilidad 15V AC rms 1 0 5 dígitos 1 5 10 dígitos Frecuencia Rango Automático Ciclo de Trabajo Frecuencia a través de los cables de prueba cuando el medidor está ajustado a voltaje AC 40Hz a 1kHz 20 a 80 1 0 5 dígitos 1 5 10 dígitos Frecuencia Rang...

Page 21: ... del producto se hará bajo la determinación de Southwire y a su discreción SOUTHWIRE NO GARANTIZA QUE ESTE PRODUCTO SERÁ COMERCIABLE O ADECUADO PARA ALGÚN PROPÓSITO EN PARTICULAR SOUTHWIRE NO HACE NINGUNA OTRA GARANTÍA EXPRESA O IMPLÍCITA SALVO QUE LA GARANTÍA ESPECÍFICAMENTE MENCIONADA EN ESTE PÁRRAFO SOUTHWIRE NO SERÁ RESPONSABLE DE DAÑOS INCIDENTALES CONSECUENCIALES INDIRECTOS ESPECIALES O PUNI...

Reviews: