Page 13 of 26
Installation & Adjustment Procedures
4. With male blade in closed position, adjust and level male blade plug to be
centered over bearing housing. Use jacking bolts (
) to make these
adjustments.
Figure 3: Rotating Insulator Bearing Housing
5. Install female blade, level and adjust to mate with male blade. The synchronizing
linkage may require slight adjustment to ensure that both blades center together
in the closed position. Set stop adjustment bolts on bearing housing for the
closed position.
6. Adjustment of switch in the open position – Rotate the insulator stacks to the
open position. The blades should travel 90 degrees. Set stops on bearing
housing to provide 90 degree blade opening. Refer to
. Open position
stop is on female blade side.