SERVICE CONNECTIONS
Gas installation to conform to local codes or in absence of local codes to national fuet gas
code —
ANSI 2223.1 —
latest edition. In Canada, installation to be in accordance wilh
CAN
/
CGA
8149.1 (NAT) or B149.2 (LP) installation codes
and/or local codes.
1. The appliance and its individual shut ofl valve must be disconnected Irom the gas supply piping system during any
pressure testing of that system at pressures in excess of 1/2 psig (3.45 kPa).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 /2 psig (3.45
RPa).
Electrical grounding must be provided in accordance with local codes, or in the absence of local codes, with the
national electric code. ANSl/NFPA 70 - latest edition. In Canada installation must be in accordance with the C.S-A.
C22.1 Canadian electrical code. part 1.
INSTALLATION INSTRUCTIONS
1. Ideally
an
exhaust system should be located directly above the appliance to exhaust combustion gases generated
by the unit.
2. Appliance is intended for use on non combustible floors. Minimum clearance from combustible and
noncombustible floor construction, 3" (.76mm> on-sides and 6"d52nnn)l from bade.
3. Set the appliance in place and level using spirit level.
4. Mark hole locations on floor through anchoring holes provided in flanged adjustable feet.
5. Remove appliance and drill holes in locations marked on floor and insert proper anchoring devices.
6. Set unit back in position and re-level left to right and front to back.
7. Bolt and anchor appliance securely to the floor.
8. Seal bolts and flanged feet with silastic or equivalent compound.
9. Appliance location must allow air supply to unit and obstruction free clearance for air opening in to the combustion
chamber.
10. Make service connections as indicated.
-5-