Installation Instructions
Test Operation
The Source 1 thermostat has a diagnostic feature that enables testing of
all outputs. This feature is contained in
Technician Setup.
To enter Technician Setup, press and hold the SETUP button for 10 seconds until
all the icons appear. Follow the next steps to view settings and test equipment.
1. Press
MODE
to view the version numbers of the thermostat.
2. Press
MODE
again to view the jumper settings and current state of the Dry
Contact terminals.
3. Press
MODE
again and the scrolling display will read “
TURN ON
EQUIPMENT
?” Press
WARMER
for Yes or
COOLER
for No.
If Yes is chosen, press
WARMER
to turn on heat or
COOLER
to turn on
Cooling. The scrolling display will read “
NOTHING ON
.” Next:
Press
WARMER
to turn on and cycle up through the heating stages.
Press
COOLER
to turn the heating stages off. Press
MODE
to exit.
Press
COOLER
to turn on and cycle down through the cooling stages.
Press
WARMER
to turn the cooling stages off. Press
MODE
to exit.
4. Press
MODE
until “CALIBRATE SENSORS?” appears on the scrolling display.
Press
WARMER
for Yes or
COOLER
for No. Press
MODE
to select which
sensor to calibrate. Use
WARMER
or
COOLER
to modify your selection.
To exit Technician Setup at any time, press the SETUP button. Technician Setup
will automatically exit after 10 minutes if no buttons are pressed.