Dry Contact Operation
Dry Contact Polarity
(Setup Step 47)
Open (Normally Open)
- The dry
contact is open until the connected
device closes the circuit.
Dry Contact Use
(setup step 48)
CONDENSATE -
If CONDENSATE is selected when the dry contact is active, the
thermostat will lockout the compressor terminal(s) and “CONDENSATE PAN
OVERFLOW” will appear on the display.
VACATION
- If VACATION is selected when the dry contact is active, the
thermostat will be forced into AWAY/unoccupied settings.
FDD
- If FDD is selected when the dry contact is active, the scrolling display will
read “Equipment fault”.
This error message will disappear when the Dry Contact is idle.
Skyport
(Setup step 49)
Set to ON to allow access to Skyport services or to OFF to not allow access to
Skyport services. (Wifi accessory is required)
Visit source1.skyportcloud.com/ for more information.
Local API
(Setup step 50)
Set to ON to allow third-party software to interface with your thermostat.
Typically used with home automation set-ups. (Wifi accessory is required)
Closed (Normally Closed)
- The dry
contact is closed until the connected
device opens the circuit.
Dry
Contact
‘Idle’
‘Active’
Dry
Contact
Dry
Contact
‘Idle’
‘Active’
Dry
Contact
29
Installer Setup