27
12.9 Room controller
Menu 7.6
Special functions
Menu 8
12
12
12.9.1 Room controller
Menu 7.6.1
12.9.2 Room reference day
Menu 7.6.2
The desired room temperature for day mode. As long as this temperature is
not reached, the reference
fl
ow temperature is raised or respectiveley lowered
according to the percent setting in “room controller”. If “room controller” is set
to 0%, this function is deactivated.
Settings range: 10 °C to 30 °C / Default: 20 °C
12.9.3 Room reference night
Menu 7.6.3
The desired room temperature for night mode. As long as this temperature is
not reached, the reference
fl
ow temperature is raised or respectiveley lowered
according to the percent setting in “room controller”. If “room controller” is set
to 0%, this function is deactivated.
Settings range: 10 °C to 30 °C / Default: 20 °C
The settings necessary for the optional room controller RC21 are made in this
menu.
The 3 modes “continous day”, “continous night” and “Time controlled/automatic”
can be switched at the RC21.
Additionally the reference temperature of the
fl
ow can be parallel translated by
turning the control wheel. If the wheel is set to minimum, only the minum values
that can be set in the protective functions menu will be used.
This value is used to appoint the amount of in
fl
uence in percent the room
temperature has on the reference
fl
ow temperature. For every degree of
deviation of the room temperature from the reference room temperature the
percentage of the calculated reference
fl
ow temperature set here is added to
or, respectively, subtracted from the reference
fl
ow temperature. As long as
it is within the limits of the min. and max.
fl
ow temperatures that can be set in
the protective functions.
Example: Reference roomtemp.: e.g. 25 °C ; room temp.: e.g. 20 °C = 5 °C
deviation.
calculated reference temp..: e.g. 40 °C : room controller: 10 % = 4 °C
5 X 4 °C = 20 °C According to this 20 °C are added to the reference
fl
ow
temperature, resulting in 60 °C. If the value is higher than the one set in max.
fl
ow temp-, the resulting temperature is only the one set in max.
fl
ow temp.
Settings range: 0 % to 20 % / Default: 0
Caution
In the operating modes “Reference value” and 14day ref.” the remote