25
12.2 Commissioning
Menu 7.2
Starting the commissioning help guides you in the correct order through the
basic settings necessary for commissioning, and provides brief descriptions of
each parameter in the display.
Pressing the “esc” key takes you back to the previous value so you can
look at the selected setting again or adjust it if desired. Pressing the “esc”
more than once takes you back to the selection mode, thus cancelling the
commissioning help. (see also 5.1)
Caution
May only be started by a specialist during commissioning! Observe
the explanations for the the individual parameters in these
instructions, and check whether further settings are necessary for
your application.
12.3 Factory settings
Menu 7.3
All of the settings that have been made can be reset, thus returning the
controller to its delivery state.
Caution
The entire parametrisation, statistics, etc. of the controller will be lostir-
revocably. The controller must then be commissioned once again.
Special functions
Menu 8
12
12
12. Special functions
Menu “7. Special functions” is used
to set basic items and expanded
functions.
The menu is closed by pressing
“esc” or selecting “Exit special func-
tions”.
Caution
12.1 Sensor calibration
Menu 7.1 / 7.1.1 - 7.1.6
Deviations in the temperature values displayed, for example due to cables which
are to long or sensors which are not positioned optimally, can be compensated
for manually here. The settings can be made for each individual sensor in steps
of 0.5°C.
Offset S1...S6 per settings range : -10°C...+10°C Default : O°C
Caution
Settings are only necessary in special cases at the time of initial
commissioning by the specialist. Incorrect measurement values
can lead to unpredictable errors.
The settings in this menu
should only be made by a
specialist.