19
The operating mode “Manual” may only be used by specialists for
brief function tests, e.g. during commissioning!
9.3 Manual
Menu 4.2
In Manual mode the individual relay outputs and the connected consumers
can be checked for proper functioning and correct assignment.
Function in manual mode:
The relays and thus the connected consumer are switched on and off by
pressing a key, with no regard to the current temperatures and the parameters
which have been set. At the same time, the current measurement values of
temperature sensors are also shown in the display for the purposes of function
control.
Danger
9.4 14 day reference
Menu 4.4
If operating mode “14 day reference value” is selected (Menu 4.1), the reference
fl
ow temperature for each of the 14 days can be set here.
In the
fi
rst menu 4.4.1 the starting time of the program is shown. To start the
program, hit restart.
Hitting “restart” again will reset the 14 day reference program and start it at
day 1.
9. Operating modes (continued)
9.3 Heat circuit reference
Menu 4.3
If operating mode “Reference value” is selected, (Menu 4.1), the reference
fl
ow
temperature has to be set here, regardless of the curve/outdoor temperature.
Settings range: 10 °C to 75 °C
Default: 30 °C
Operating modes
Menu 4
9
9