17
Instruction for use | Supercal 5
Check the design data of the components.
The flow sensor’s pulse factor and location must correspond to the datasheet values;
check the type plates!
The permissible ambient temperature for the calculator is 5 ... 55 °C.
The installation and project planning regulations must be adhered to.
The calculator faceplate and all nameplates must be legible.
The complete heat meter consists of the following three subunits:
Flow sensor
Calculator Supercal 5
Temperature sensor (2- or 4-wire technology) with or without pockets
The pulse factor set in the calculator must match that of the flow sensor, the temperature
sensor resistance set in the calculator must also match the temperature sensor.
The Supercal 5 calculator offers the following mounting options:
4.6.2 Wall Mounting