4.6 Mounting
4.6.1 Before Mounting
All cables must be laid
at least 300 mm away from
power and high-
frequency cables.
Radiant heat and electrical interference fields in the vicinity of the
calculator must be avoided.
The calculator must generally be mounted away from the hot or cold
pipes.
Ensure no condensation can run into the calculator along the connected
lines.
If there is a risk of vibration in the piping system, the calculator should
be mounted separately on the wall.
For medium temperatures above 90 °C, the calculator should be
mounted separately.
The flow sensor should be mounted between two shut-off valves.
The direction of flow in the flow sensor must be adhered to (arrow on
the flow sensor).
The pipeline must be flushed before mounting the flow sensor to ensure
that there are no foreign bodies in the pipeline.
The lines must be vented during commissioning. Air in the system or in
the flow sensor can impair the measurement result.
Only use suitable new sealing material.
The tightness of the various connections must be checked.
Lightning protection cannot be guaranteed; this must be ensured via
the house installation.