6 | Electrical installation
32 / 60
Installation instructions sonnenBatterie eco 9.43
6.4 Connecting the mains line
DANGER
Electrical work on the storage system and electrical distributor
Danger to life due to electrocution!
Switch off the storage system to electrically isolate it.
Disconnect the relevant electrical circuits.
Secure against anyone switching on the device again.
Wait five minutes so the capacitors can discharge.
Check that the device is disconnected from the power supply.
Only authorised electricians are permitted to carry out electrical work.
Connect the wires for the mains line as shown in Figure ‘Circuit diagram overview
– electrical connection at single-phase mains [P. 26]’ or ‘Circuit diagram overview
– electrical connection at three-phase mains [P. 27]’. Make sure that the mains
line’s coloured wires are correctly connected.
N
L
PE
Illustration 36: The assignments of the coloured wires in the mains line
Connect the socket (4) of the public network to the (XAC) connection on the
storage system. Ensure that the stickers (1, 2) face upwards.
Close the lock (3).
1
2
4
3
XAC
Illustration 37: Connection of the mains line to the connection socket
1, 2
Sticker
3
Lock
4
Mains connection socket
XAC
Mains connection on the storage system