5 Electrical installation
DANGER
Electrical work on the storage system and electrical distributor
Danger to life due to electrocution!
Switch off the storage system to electrically isolate it.
Disconnect the relevant electrical circuits.
Secure against anyone switching on the device again.
Wait five minutes so the capacitors can discharge.
Check that the device is disconnected from the power supply.
Only licensed electricians are permitted to carry out electrical work.
DANGER
Touch voltage in the event of a fault during backup operation
Danger to life due to electrocution!
A residual current device (RCD) must be installed downstream of the output
of the Backup-Box.
NOTICE
Observe maximum line lengths
None of the lines connected to the Backup-Box and the storage system
(mains line, ethernet line, other data lines) are allowed to exceed a maximum
length of 30 m.