LC-RL-8-W User Manua
l
Sonetonix
8
5.3 Examples
Command
Description
Get Device Info for ID 2
$02 $F2
Set New Device ID to ID 3 as 8
$FE $03 $F3 $08 $FD
Force Set Device ID of a new ID to 01
$FE $F4 $01 $00 $FD
Turn ON all channels to device ID 05
$FE $05 $FA $00 $FD
Turn OFF all channels to device ID 05
$FE $05 $F9 $00 $FD
Get Device Status of device ID 01
$01 $F1
Set Load 1 to ON immediately ID 01
$FE $01 $01 $01 $00 $00 $FD
Set Load 1 to OFF immediately ID 01
$FE $01 $01 $00 $00 $00 $FD
Set Load 1 to ON after 5 seconds ID 02
$FE $02 $01 $01 $00 $05 $FD
Store scene to device ID 01 – ch1 ON ch4 ON with
scene number as 05 (2 channels in scene)
$FE $01 $F7 $02 $05 $01 $01 $00
$00 $04 $01 $00 $00 $FD
Recall scene 5 for device ID 01
$FE $01 $F8 $05 $FD
Set multiple control command to ON load 1 and
Off load 2 after 5 seconds ID 01
$FE $01 $F6 $02 $01 $01 $00 $00
$02 $00 $00 $05 $FD
6. Troubleshooting
Trouble
Cause
Corrective Action
Load
Switching not
happening
Switch connection
Check the connection in load
side
Watchdog LED does not
blink
Relay module not functioning
Reset the device
Communication Failure
Switching not
happening with S-NET
Commands
Serial communication failure
(a) Check the RS485
cabling of S+ and S-
connections with other
units
(b) Verify functionality
manually
Get status does not
match the actual status
Communication failure
a) Check the Device ID
configured and used
b) Check the baud rate
c) Check the command
codes