LC-RL-8-W User Manua
l
Sonetonix
7
5. S-NET Communication
The
LC-RL-8-W
can be connected in S-NET with other Automation modules using
RS485 serial interface. The signal connection is shown in Fig 1. Wiring diagram
5.1 Communication parameters
Parameter
Description
Signal Level
RS-485 compliant
Synchronisation method
Asynchronous
Baud Rate
38400 bits / second
Parity
None
Data Bits
8
Stop Bits
1
5.2 S-NET Commands
Using the S-NET protocol command codes, various features of the
LC-RL-8-W
can
be controlled and used. The device control commands and channel control commands
are described here under.
Command
Description
Response
Get Device Info
<ID> $F2
$F5 <ID> <Device Type>
<Device model> $F5
Get New Device Info
$F0 $F2
$F5 <ID> <Device Type>
<Device model> $F5
Set New Device ID
$FE <ID> $F3 <new ID>$FD
$F5 <ID> <ch1 status> <ch n
status> $F5
Force Set Device ID
$FE $F4 <new ID> $00 $FD
$F5 <ID> <ch1 status> <ch n
status> $F5
Get Device Status
<ID> $F1
$F5 <ID> <ch1 status> <ch n
status> $F5
Turn ON all channels
$FE <ID> $FA $00 $FD
None
Turn OFF all channels
$FE <ID> $F9 $00 $FD
None
Set Load to ON
immediately
$FE <ID> <Ch.no> $01 $00 $00
$FD
None
Set Load to OFF
immediately
$FE <ID> <ch.no> $00 $00 $00
$FD
Multiple channels
control
$FE <ID> $F6 <no.of channels>
<ch1. Data>…..<ch n. Data>
$FD
None
Store scene
$FE <ID> $F7 <no.of channels>
<Scene.no> < ch1.
Data>….<ch n.data> $FD
None
Recall scene
$FE <ID> $F8 <scene. No>$FD None
Set Load status after
delay
$FE <ID> <ch.no> $xx $00 $yy
$FD
None