GETTING STARTED

-  If  you  wish  to  activate  one  of  the  functions,  first 

make sure you know what resources the function 
needs,  the  type  (fixed,  exclusive  or  shared)  and 
check  that  the  configured  system  leaves  the 
required resources available:

- Seven PT1000 probes (S1, S2, ..., S7)
- Six 5A 250 V~ relays (R1, R2,..., R6)
- 1 pulse input (Calorimeter).

These  resources  are  shared  by  systems  and 
functions in different ways.

The  probes  and  relays  in  the  systems  are  pre-
assigned and non-configurable. The probes can be 
shared by the systems and the functions

The relays cannot be shared between systems and 
functions (except the OR and AND functions).

The screen only shows the available systems, relays 
and probes, depending on the activated functions and 
systems. 

If you need a function or system which is not shown, 
you will have to free the required resources first.

The Allegro 

576

 is a thermal solar regulator. 

On the screen you can see diagrams showing all the 
information required to quickly and easily configure 
and adjust your installation.

In  normal  operation  mode,  the  screen  shows  the 
status  of  the  devices  (pumps,  relays,  alarms,  etc.) 
and the probe temperatures.

For  optimal  operation  carefully  read  this  section, 
which  indicates  the  steps  to  follow  to  adapt  the 

Allegro 576

 to your installation.

Steps to follow:

-  Once  installed  and  once  the  connections  have 

been made, you can connect the Allegro 576 to the 
mains.

- Before configuring the system values and settings 

it  is  advisable  to  test  the  probes  and  relays  to 
check  the  correct  operation  of  the  installation. 
(This step is explained on page 9.)

- Once you have verified the operation, choose the 

system that best suits your installation type from 
among the available configurations (pages 22 and 
23).  Remember  that  System  1  has  6  variants 
depending on the number of accumulators to be 
configured,  although  only  1  symbol  is  shown  on 
the screen.

- All the settings are preset to factory default values. 

If  these  values  do  not  suit  the  needs  of  your 
installation, consult page 26 to configure them.

8

OPERATION

ESC

OK

576

Sonder

Accumulator cooling

This parameter allows you to reduce the temperature of the accumulator by 

recirculating the collector, when it detects that the collector temperature is 
lower than the accumulator temperature.

- In the 

SETTINGS

 menu press                  until the

REFRIG ACUMULADOR

 screen appears.

- Press 

OK

 to enter the function settings, and use                           to define the 

desired value.

- Press 

ESC

 to go back and press 

OK

 to save the adjusted values.

Range:  5 ºC to 130 ºC   /   Default: 130 ºC

ESC

OK

576

Sonder

29

SETTINGS

Display light

Parameter that defines the type of display lighting: timer (15 minutes without 

keyboard activity) or always on.

- In the 

SETTINGS

 menu press              until the 

LIGHT

 screen appears.

- Press 

OK

 to enter the function settings, and use                           to define the 

desired value.

- Press 

ESC

 to go back and press 

OK

 to save the adjusted values.

Range:  OFF(15 min. and when a key is touched)
              ON   (always on)                                           /   Default:   OFF

ESC

OK

576

Sonder

Password

This  parameter  denies  unauthorised  access  to  the  Allegro  576 
configuration. The user can only view statistics, screen light, change 
summer/winter and perform the probe and relay tests.

- In the 

SETTINGS

 menu press                         until the

 PASSWORD

 screen 

appears.

- Press 

OK

 to enter the function settings, and use                           to define the 

desired value.

- Press 

ESC

 to go back and press 

OK

 to save the adjusted values.

Range:  

 ( )    to    

 (

)   /   Default:   

 ( )

OFF 0

ON 1...9999

OFF 0

ESC

OK

576

Sequential priority

This parameter defines the charging priorities according to the accumulator 
number, if the installation has more than one. (see page 31).

- In the 

SETTINGS

 menu press                 until the 

PRIO SECUENCIAL

 screen 

appears.

- Press

 OK 

to enter the function settings, and use                           to define the 

desired value.

- Press 

ESC 

to go back and press 

OK

 to save the adjusted values.

Range:  OFF  to   ON   /   Default:   OFF

ESC

OK

576

Sonder

S S

S S

S S

S S

S S

S S

S S

S S

MENU

Summary of Contents for Allegro 576 BOX

Page 1: ... Manual Energy control Avenida la Llana Nº 93 P I La Llana 08191 RUBÍ Barcelona Spain Tel 34 93 588 42 11 Fax 34 93 588 49 94 www sonder es info sonder regulacion com SONDER REGULACIÓN S A Allegro 576 RAIL code 20 043 Allegro 576 BOX code 20 054 ...

Page 2: ...5815VØ MAY 09 2 35 NOTES ...

Page 3: ...scription Technical specifications Dimensions Connections Operation Getting started Probe and relay test Screen view Configuration Factory settings and resetting Resource control Menu Statistics Functions Systems Settings 33 4 5 6 6 6 6 7 8 8 9 10 11 12 13 16 16 18 22 26 ...

Page 4: ...modify the product technical data and assembly and use instructions without prior notification WARRANTY CONDITIONS This device has Three year warranty The warranty is limited to the replacement of faulty parts which will be restored to the same condition in which they were received No packaging batteries instructions or any other accessories included with the product will be replaced We cannot acc...

Page 5: ...3 channels 3 alarms Telephone control landline mobile 1 channel 1 alarm Water meter with pulse output L 50mm L 100mm L 200mm Conductive paste for sheaths 5 PRESENTATION Stainless steel sheaths GSM Consult us about models for remote management and data storage with SD card Visit our WEBSITE New products All our products Technical documentation Catalogues www sonder es Consult our wide range of prod...

Page 6: ... has reached 45 the swimming pool is heated to dissipate the excess heat instead of accumulating it in the collectors thus preventing the installation from overheating Example with system 6 2 Accumulator priority ºC AC 1 AC 2 AC 3 65 40 5 H W U H Swimming pool In summer Tank alarm ºC AL 1 AL 2 AL 3 70 45 35 Since the underfloor heating does not need to be activated during the summer its priority c...

Page 7: ...each type of system If they are of use to you the device is ready to control and regulate your installation If due to the needs of your installation you require other settings read this section carefully In the menu you can adjust the parameters that define how the installation will operate default values and setting ranges SETTING RANGE ADJUSTED Adjustment mode Activation differential Deactivatio...

Page 8: ...lthough only 1 symbol is shown on the screen All the settings are preset to factory default values If these values do not suit the needs of your installation consult page 26 to configure them 8 OPERATION ESC OK 576 Sonder Accumulator cooling This parameter allows you to reduce the temperature of the accumulator by recirculating the collector when it detects that the collector temperature is lower ...

Page 9: ...key the system returns to normal operation and the relays return to the status required by the system at that time With the password OFF The system does not exit the test menu until the ESC key is pressed forced manual mode Then move on to the relays forced manual where you can manually activate deactivate each relay Press OK to activate deactivate relay R1 Press to move on to the next relay Press...

Page 10: ...LIGHT TIMER LIGHT parameter OFF 10 ESC OK 576 Sonder This screen informs you that The probe assigned to the radiator has a reading error S S OPERATION SETTINGS 27 Tank temperature alarm This parameter defines a temperature alarm for each accumulator depending on the system a unit heater or cooling system is activated another accumulator is charged or circulation is stopped In the PARÁMETROS menu p...

Page 11: ...to move to PARÁMETROS and then press OK In the menu you can adjust the settings that will define the operation of the installation Winter or summer mode Activation differential Deactivation differential Temperature alarm in tanks 1 to 6 Temperature differential general for all settings Minimum setting limit Maximum setting limit Minimum ambient limit Maximum ambient limit Separate calibration for ...

Page 12: ...limit Maximum setting limit Active system 1 1 1 tank 1 pump If the password is activated it is impossible to reset the values and restore the factory settings To do so it is necessary first to deactivate the password value 0 in the settings menu If an unauthorised user tries to reset the values he would press the ESC key for 10 seconds and only be able to enter the probe and relay test When you ex...

Page 13: ...3 3 1 3 2 3 3 5 1 5 2 5 3 6 1 6 2 6 3 4 1 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 13 OPERATION Hot water S4 S5 R3 S3 R5 R2 S1 S7 R6 A B C D EXCHANGER PURIFIER F R1 R4 S6 E S1 S2 S3 S4 S5 S6 S7 R1 ...

Page 14: ... S S S S S OK S S S S S S S S S S S S S S S S ESC S S S S S S S S S S OPERATION collector array 2 pumps 2 tanks collector array tank swimming pool 2 pumps collector array tank heating 2 pumps collector array 2 tanks pump 3 way valve collector array tank swimming pool pump 3 way valve collector array tank heating return pump 3 way valve 2 collector arrays east and west 2 tanks 2 pumps 3 way valve 2...

Page 15: ...n Use the keys to move on to the next system To confirm the chosen system press OK and press the ESC key to return the previous menu Once the system has been configured the unit saves the changes and returns to normal operation SYSTEMS The representation of the units on these diagrams is symbolic One solar panel means there is one array of solar collectors but when there are 2 it means that there ...

Page 16: ...e solar system you need for your installation and then the functions since you may not be able to configure the rest of the functions according to relays the systems leaves frees MENU Thermostat 1 2 3 independent Thermostat 1 2 ambient Anti frost Double pump alternation Cooling by unit heater Calorimeter Tubular sensor Return increase OR AND Regulates the temperature of a probe heating underfloor ...

Page 17: ...s ESC to return to the FUNCIONES menu This function conditions the status of a relay based on the status of all the selected relays For example if you choose R1 as the slave relay and R2 R4 and R6 as the main relays R1 will be activated when R2 AND R4 AND R6 are activated When any one of the main relays is off the slave relay switches off AND ESC OK 576 FUNCTIONS 20 Press OK to enter the function ...

Page 18: ...to enter the function settings where you can activate deactivate the function and set the total time that each pump will operate before changing 4 to 120 hours Press to change the flashing value and press OK to confirm the selection Press ESC to return to the FUNCIONES menu S S This function allows you to double a pump in your installation so that the two pumps work in alternation Double pump alte...

Reviews: