Independent thermostat 1
Independent thermostat 2
Independent thermostat 3
Ambient thermostat 1
Ambient thermostat 2
Anti-frost protection
Double pump alternation function
FUNCTIONS
The functions use the probes shared by the systems and the relays left free by
the systems and other functions.
If you try to configure more functions than supported by the unit, the VOID
message will appear on the screen and it will exit the function.
Activation of cooling by unit heater
Calorimeter
Specific function for tubular sensors
Increase of the return temperature from the heating
circuit
OR function
AND function
18
Independent thermostat
ESC
OK
576
Sonder
- Press
OK
to enter the function settings where you can activate/deactivate the
function, set the temperature to be regulated (10 to 90 ºC), the reading probe
and the relay activated. Press to change the flashing value and press
OK
to confirm the selection.
- Press
ESC
to return to the
FUNCIONES
menu
.
S S
This function allows you to install one or two remote adjustment probes (
MODERATOR SR
) in your installation. This allows you
to regulate the temperature of the room without having to change the temperature setting using the Allegro 576.
Ambient thermostat
Thermostat 2
Thermostat 1
Thermostat 3
- Press
OK
to enter the function settings to activate/deactivate the function, set the
setting probe (to select the temperature at which the room must be kept), the
regulation probe (it will take the reading of the room temperature) and the relay
to be activated. Press to change the flashing value and press
OK
to
confirm the selection.
- Press
ESC
to return to the
FUNCIONES
menu.
S
S
This function allows you to regulate the temperature of a probe (underfloor heating, central heating, thermostat, etc.) regardless
of the chosen solar system.
It has three independent thermostat functions, each one of which has a
different icon so that you can easily tell which one the data on the screen
relates to in normal mode.
Although the icons are different, they operate in the same way.
To access the functions menu, press for 5 seconds (with the screen lit), use the arrows to select the
functions
menu and then press
OK
. In the menu you will find:
Thermostat 2
Thermostat 1
ESC
OK
576
Sonder
2
Once you have configured and installed the remote probe you have to calibrate
the reading on the button of the remote terminal with the value of the Allegro 576
reading. To do this:
- Set the button of the remote probe to 20 ºC.
- Enter
menú, parámetros
and
calibrado de sondas.
- Change the value of the setting probe to 20 ºC
Example setting probe
S4
: on screen the reading from this probe is 19.5 ºC, go
to probe calibration and change the value of S4 from 0.0 to 0.5.
S S
ESC
OK
576
Sonder
MENU
19
- Press
OK
to enter the function settings, where you can activate/deactivate the
function and set the total time that each pump will operate before changing (4 to
120 hours). Press to change the flashing value and press
OK
to confirm
the selection.
- Press
ESC
to return to the
FUNCIONES
menu.
S S
This function allows you to double a pump in your installation so that the two pumps work in alternation.
Double pump alternation
ESC
OK
576
Sonder
FUNCTIONS
- Press
OK
to enter the function settings, where you can activate/deactivate the
function, set the temperature (40 to 140 ºC), the reading probe and the
recirculation or unit heater activation relay. Press to change the flashing
value and press
OK
to confirm the selection.
- Press
ESC
to return to the
FUNCIONES
menu.
S S
This function allows you to reduce the temperature of a device by recirculating the circuit or a cooling device. The configured
relay is activated when it detects that the temperature of the device is higher than the temperature of the circuit
Cooling by unit heater
ESC
OK
576
- Press
OK
to enter the function settings, where you can activate/deactivate the
function, adjust the configuration of the pulse input (1 to 200 litres per pulse), the
composition of the heat-transfer liquid (0 to 100% glycol) the input probe and the
meter probe (at the input and output of the accumulator to calculate the amount
of heat transferred). Press the keys to change the flashing value and
press
OK
to confirm the selection.
- Press
ESC
to return to the
FUNCIONES
menu.
S S
This function measures the amount of energy supplied to your installation by the solar collector by reading two probes (one
at the input and the other at the output of the part of the installation you want to control) and the pulse input (it measures
the flow rate of the installation).
Calorimeter
ESC
OK
576
Sonder
- Press
OK
to enter the function settings, where you can activate/deactivate the
function, set the temperature at which the pump is to be activated (-20 to 20 ºC)
and the relay that will circulate the water from the accumulator through the circuit
of the installation to the solar collector. Press to change the flashing
value and press
OK
to confirm the selection.
- Press
ESC
to return to the
FUNCIONES
menu.
S S
The anti-frost function has been designed for installations that use water as a heat-transfer liquid. Since it does not contain any
anti-freeze, the heat of the installation is used to prevent the circuit from freezing.
Anti-frost
ESC
OK
576
Sonder
- Press
OK
to enter the function settings, where you can activate/deactivate the
function. Press to change the flashing value and press
OK
to confirm the
selection.
- Press
ESC
to return to the
FUNCIONES
menu.
S S
This updates the reading of the probes installed outside the collectors by recirculation for 30 seconds when it detects that the
temperature has increased 2K with regard to the last memorised reading.
Tubular sensors
ESC
OK
576
Sonder
MENU