2017 SOMFY ACTIVITÉS SA, 50 avenue du Nouveau Monde, 74300 Cluses, France REF. 5135987B – 2017-06-30 

Page 1/8

 

 

Operation and installation manual 

KNX IP LineMaster

 

Ref. 9018249B 

KNX Power supply with integrated KNX IP Router and diagnosis functions 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

KNX IP LineMaster 

 

Application 

The KNX LineMaster combines the essential functions of a KNX 

bus line: Power supply with choke, KNX IP Router and KNX IP 

Interface with a small footprint of only 6 units (108 mm). 
The KNX IP Router in the KNX IP LineMaster allows forwarding 

of telegrams between different lines through a LAN (IP) as a fast 

backbone. In addition this device is suited to connect a PC to the 

KNX network e.g. for ETS® programming. 
The IP address can be obtained by a DHCP server, by manual 

configuration via the device menue or by downloading a config-

ured ETS application. This device works according to the 

KNXnet/IP specification using the core, the device management, 

the tunneling and the routing part. 
The KNX IP LineMaster has a filter table (8 kByte) and is able to 

buffer up to 150 telegrams. 
An easy to read OLED display on the front panel enables the 

user to display the operating parameters locally on the device. 

Coupler function (KNXnet/IP Routing) 

 

The KNX IP LineMaster operates as a line or backbone coupler. 

In both cases, the LAN (IP) is used as a backbone. 

The following table shows the application possibilities of the KNX 

IP LineMaster compared to the classic topology: 

 

 

Classical  

Topology  

(without IP) 

IP coupling   

of areas 

(IP area coupl.) 

IP coupling  

of lines 

(IP line coupler) 

Area 

(Backbone) 

TP 

IP 

IP 

Coupling 

KNX Line Coupler 

(max. 15 Pcs.) 

KNX IP Router 

(max. 15 Pcs.) 

Directly via 

LAN Switch 

Main line 

TP 

TP 

IP 

Coupling 

KNX Line Coupler 

(max. 15x15 Pcs.) 

KNX Line Coupler 

(max. 15x15 Pcs.) 

KNX IP Router 

(max. 225 Pcs..) 

Line 

TP 

TP 

TP 

 

 

KNX IP LineMaster as line coupler 

 

The individual address assigned to the KNX IP LineMaster de-

termines whether the device operates as a line or area coupler. If 

the individual address is in the form of x.y.0 (x, y: 1..15), the KNX 

IP LineMaster operates as a line coupler. If it is in the form of 

x.0.0 (x: 1..15), the KNX IP LineMaster acts as a backbone 

coupler. 

 

 

 

KNX IP LineMaster as area coupler 

 

If the KNX IP LineMaster is used as an area coupler 

(x.0.0), there must not be a KNX IP Router in the topolo-

gy beneath it. For example, if a KNX IP Router has the 
individual address 1.0.0, there must be no KNX IP Rout-

er with the address 1.1.0. 

If the KNX IP LineMaster is used as a line coupler 

(x.y.0), there must not be a KNX IP Router in the topolo-

gy above it. For example, if a KNX IP Router has the in-

dividual address 1.1.0, there must be no KNX IP Router 

with the address 1.0.0.

 

 

EN 

 

 

 

Summary of Contents for KNX IP LineMaster

Page 1: ...aster operates as a line or backbone coupler In both cases the LAN IP is used as a backbone The following table shows the application possibilities of the KNX IP LineMaster compared to the classic top...

Page 2: ...flashes quickly The programming mode is not active The rapid flashing indicates one of the following faults o Overload sum of the current of auxiliary and Bus power o The device is not loaded correct...

Page 3: ...nged on the subline TP ROUT Acknowledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ET...

Page 4: ...d via an ETS project See the ETS database section for more information As factory default the assignment of the IP address is set to automatically via DHCP no further IP settings are necessary To use...

Page 5: ...changes in the properties menu become effective on ly after a successful application download IP address Here the IP address of the KNX IP LineMaster can be entered This is used to address the device...

Page 6: ...e routed to IP Route All group telegrams of this main group are routed to IP independent of the filter table This setting is used for testing purposes on ly Filter The filter table is used to check wh...

Page 7: ...ived group telegram should be routed to KNX TP Individually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to...

Page 8: ...be loaded via a direct IP connection at high speed The direct IP connection is possible if the device already has a valid IP configuration as well as an individual address To do this select Use direc...