Setting the detection range
The upper beam is fixed: it always remains parallel to the ground.
The lower beam can be adjusted (see below).
Given that the beams (lower and upper) must be broken simultaneously to trigger an alarm, the detector range
is limited to the range of the lower beam.
Détection !
Portée de détection
Detection!
Detection range
The lower and upper beams are
broken.
Pas de détection !
Portée de détection
Detection range
No detection!
Only the lower beam is broken.
Pas de détection !
Portée de détection
No detection!
Detection range
Only the upper beam is broken.
1
Set the range by gently sliding the lens in its housing.
(
The lower left and right-hand zones can be set
independently
).
Ensure that the lens remains parallel with the holder. DO
NOT TWIST IT.
Position/Range look-up table
(Installation height = for example 1 metre)
Position
Maximum range per side
Standard
Variations *
A
12 m
10 to 15 m
B
8 m
6 to 10 m
C
5 m
4 to 8 m
D
2 m
1.5 to 3 m
A
B
C
D
NON !
OUI
YES
NO!
* The maximum detection range may vary according to the atmospheric conditions.
2
Replace the lens holder in the front cover, aligning
the three marks (X, Y and Z) on each side of the lens
holder with the three notches (X’, Y’ and Z’) on the
front cover, ensuring that the 6 clips are correctly
inserted.
Y
X
Z
Y'
Z'
X'
Setting the sensitivity
The sensitivity selection switch has 3 positions:
H
(High),
M
(Medium) y
L
(Low).
The default sensitivity setting is
M
.
To adjust the sensitivity, select
L
or
H
.
If the angle of the beams has been changed, because of an obstacle, the sensitivity must be set to H.
1
2
3
ON
L
M
H
SENS
H
M
L
SENS