background image

                                                                                                                  

Inverter User Manual 

 

Version 1.14, June 2020 

7

you  to  scroll  manually  from  screen  to  screen  or  to  maintain  activated  an  individual 

screen (always visible), when required.  Pressing twice the central key will activate the 

screen that provides input voltage and current readings, leaving it fixed. 

 
 
5.- INVERTER PROTECTIONS

 

 

The  inverter  is  protected  against  reverse  polarity,  overload,  short-circuit,  over 

temperature  and  battery  voltages  out  of  a  reasonable  range.  Please  see  below  a 

detailed description of each of the protections.  

 

Contact  our  technical  service  (

[email protected]

)  for  factory  setting  of 

automatic restart after overload or short-circuit. 

 

 

5.1.- Overload Protection 
 

See table in section 12 for overload limits. 

  

The inverter gets latched in this condition.  To reset, the power ON / OFF switch 

is required to be switched OFF and ON again (manual start-up).   

 

Before  switching  ON  the  inverter  again,  ensure  that  the  cause  of  the 

overload is removed. 

 

 

5.2.- Over-Temperature Protection 

 

As  the  inverter  does  not  have,  logically,  100  %  performance  efficiency,  it 

dissipates the difference in form of heat, particularly when the unit is operating close to 

its  nominal  power  capacity.  When  the  inverter  is  subject  to  a  heavy  load  for  a 

prolonged period of time, the overheating protection will be triggered in three stages: 

first activating its internal fan, then if the temperature keeps increasing it reduces the 

output  voltage  by  10  %  and  if  temperature  continues  rising  it  cuts  output  voltage 

altogether. 

 

When  the  temperature  drops  down  to  a  certain  value,  the  unit  starts 

automatically. 

 

 
5.3.- High and Low Battery Voltage Protection 

 

The inverter can operate within the range of battery voltages between 5/6 and 

4/3 of its nominal voltage (10 and 16 V for a 12 V inverter). This range is adjusted in 

factory depending on the type of battery that will be used. The battery model type can 

be selected using the Installer password. 

 

Shutdown  due  to  low  DC  input  voltage  prevents  the  battery  from  fully 

discharging,  otherwise  it  can  cause  irreversible damage to the  battery.   A  delay  time 

has  been  foreseen  in  the  control  circuit  allowing  the  battery  voltage  to  drop 

momentarily below these limits; this makes it possible to start induction motors or cold 

filament lamps with this inverter. The “Low Battery Voltage” LED alarm will flash while 

Summary of Contents for SOLENER

Page 1: ...NER Pure Sine Wave Inverter User Manual Version 1 14 June 2020 Soluciones Energéticas S A Avenida Real de Pinto 146 28021 Villaverde Alto Madrid Telephone 34 91 539 27 00 www solener com solener solener com ...

Page 2: ...NGS 6 5 INVERTER PROTECTIONS 5 1 Overload Protection 7 5 2 Over Temperature Protection 7 5 3 Low and High Voltage Protection 7 6 INSTALLATION INSTRUCTIONS 6 1 Inverter Mounting 8 6 2 Wiring 8 7 START UP PROCEDURE 9 8 SHUT OFF PROCEDURE 9 9 PRECAUTIONS 9 10 MAINTENANCE 9 11 SAFETY INSTRUCTIONS 10 12 TECHNICAL SPECIFICATIONS 11 13 SERVICE CODES 11 14 WARRANTY 12 ...

Page 3: ...oes not work Start up and shutdown is possible through any PROFESSIONAL SOLENER CONTROLLER using an optional control line In addition since the beginning of 2010 almost all versions feature a relay for generator start which is activated closing a potential free contact when the battery needs recharging This relay can be configured to perform other functions see some of these possible functions in ...

Page 4: ... These element references will be used throughout this manual The small model has one multi color LED that brings together the functions of the seven LED present in rest of the models 1 Alphanumeric Screen 2 Acoustic Alarm 3 Load Disconnection Indicator 4 Shortcircuit Indicator 5 Battery Over Voltage Indicator 6 Battery Under Voltage Indicator 7 Over Temperature Indicator 8 Load Detection Indicato...

Page 5: ...When the inverter DC voltage input drops to a value lower than the re start voltage setting the inverter will re start automatically Inverters produce heat when operating The amount of heat produced is almost proportional to the amount of power supplied by the inverter When the MOSFET reaches a certain programmed temperature 50 ºC by default the internal fan is activated stopping when the temperat...

Page 6: ...attery input voltage and turns off when it drops to a safe operating voltage value Overload Red It flashes when a short circuit takes place It remains lit if it exceeds the overload preset time Load Disconnection Red It turns ON when the inverter has shut off AC output disconnected to protect the installation or the inverter itself The yellow or red LED that remains lit together with the Load Disc...

Page 7: ...s the difference in form of heat particularly when the unit is operating close to its nominal power capacity When the inverter is subject to a heavy load for a prolonged period of time the overheating protection will be triggered in three stages first activating its internal fan then if the temperature keeps increasing it reduces the output voltage by 10 and if temperature continues rising it cuts...

Page 8: ...e or with a red terminal to connect to the positive terminal of the battery A black or blue cable to connect to the negative terminal of the battery A three wire cable phase neutral and ground or an industrial connector for connection to the AC loads An optional two wire cable to connect to the remote control Battery cables have a terminal at the end which must be attached with bolts to the termin...

Page 9: ...hat adjusted with the load detection potentiometer the inverter will start and the output voltage will increase rapidly until it reaches its nominal value If not load will turn ON and OFF once per second Verify that the RCD is working properly by pressing the test button on the front if it trips then it is working properly This cross check must be done occasionally as indicated by the manufacturer...

Page 10: ...e battery correctly Overload or short circuit Load Disconnection and Shortcircuit if applicable LED alarms will turn on Turn OFF the inverter eliminate the cause of shortcircuit or overload and turn on the inverter again High Battery voltage Load Disconnection and High Battery Voltage LED alarms turn on Inverter automatically restarts beware when battery voltage drops to reconnection voltage Low B...

Page 11: ...gth mm 115 315 315 315 460 460 460 535 535 535 647 Height mm 230 118 118 118 157 157 157 178 178 178 210 Width mm 154 192 192 192 255 255 255 285 285 285 344 Net Weight kg 4 9 9 12 20 22 22 24 36 36 68 Relay see Section 1 NO NO NO NO NO YES YES YES YES YES YES PROTECTIONS Against Reverse Polarity using intelligent diode Against High and Low Voltage Against Shortcircuit and Overload Against Over Te...

Page 12: ... examine and test the product according to prevailing rates The warranty is solely limited to the repair materials and labor of the equipment in no case includes travel expenses freight or shipping costs or any damage caused by the use of or inability to use the equipment The use of our products in life support devices without the express written permission of our company President is specifically...