background image

                                                                                                                  

Inverter User Manual 

 

Version 1.14, June 2020 

5

 
3.- INVERTER OPERATION 

 

After switching ON the inverter, the unit carries out system checking sequences; 

if an error is detected the failure cause will be shown on the LCD display and the Load 

Disconnection  LED  Indicator  will  start  to  flash  along  with  other  LED  indicators 

(depending  on the failure). This  type  of failure  does  not  allow  the  inverter  to function 

properly therefore it will cut power supply to the load. As part of this self-test process 

the internal inverter fan will run for 1 second. 

 

After  the  self-test  process,  the  AC  output  voltage  will  gradually  increase  from 

zero to its nominal value (soft start). If the load detection circuit is active and does not 

find loads greater than those predetermined, then the inverter will go into load detection 

(stand-by) mode reducing its power consumption and checking again once per second. 

 

When  the  battery  voltage  is  lower  than  the  “low  battery  voltage”  setting,  the 

acoustic alarm is activated and the “low battery” LED alarm begins flashing once per 

second.  After 10 seconds this LED alarm will remain lit and the “Load Disconnection” 

LED  will  turn  ON  too,  indicating  that  the  inverter  has  been  shut-off.  If  the  battery 

voltage rises reaching a voltage above the predetermined restart voltage, the inverter 

will automatically start and both LED will turn OFF. 

    

If the battery voltage reaches 4/3 of the inverter rated battery input voltage (e.g. 

16 volts in a 12 volt inverter) the “Battery Over Voltage” LED turns ON in conjunction 

with the “Load Disconnection” LED causing the AC

 

output to shut-down.  When the 

inverter DC voltage input drops to a value lower than the re-start voltage setting, the 

inverter will re-start automatically. 

 

Inverters  produce  heat  when  operating.  The  amount  of  heat  produced  is 

(almost)  proportional  to  the  amount  of  power  supplied  by  the  inverter.    When  the 

MOSFET  reaches  a  certain  programmed  temperature (50  ºC  by  default),  the  internal 

fan  is  activated,  stopping  when  the  temperature  drops  below  the  preset  temperature 

limit  (factory  default  is  40  ºC).  However,  if the  temperature keeps  on rising  (because 

the connected load is too high) and reaches 60 ºC, the output voltage will decrease by 

10 % in order to reduce the power; if despite this the temperature keeps rising, the unit 

will  shut  off  when  the  temperature  reaches  80  ºC,  restarting  again  at  60  ºC.  System 

shutdown due to over temperature will be indicated by the corresponding yellow LED 

alarm simultaneously with the “load disconnection” red LED (the screen also indicates 

the  cause  of  the  load  disconnection).  While  the  system  is  disconnected  due  to  over 

temperature the fan will continue functioning. 

 

In models with input control, if this is not activated, the inverter will shut down 

and  the  “Load  Disconnection”  LED  indicator  will  turn  on.  When  it  is  activated,  the 
inverter  restarts  shutting  off  the  correspondent  LED  alarm.  Input  control  activation  is 
made by closing a circuit. 

 

If a short-circuit is produced at the inverter output, the unit automatically limits 

the  output  power  to  protect  the  installation,  and the  short-circuit  LED  lights  up. If  the 

short-circuit lasts more than 10 seconds then the “Load Disconnection” LED will  light 

up and the inverter will stop. Once the cause of the short-circuit has been eliminated it 

is  necessary  to  reset  the  unit  (using  the  ON/OFF  switch)  in  order  to  recover  the  AC 

output.   

Summary of Contents for SOLENER

Page 1: ...NER Pure Sine Wave Inverter User Manual Version 1 14 June 2020 Soluciones Energéticas S A Avenida Real de Pinto 146 28021 Villaverde Alto Madrid Telephone 34 91 539 27 00 www solener com solener solener com ...

Page 2: ...NGS 6 5 INVERTER PROTECTIONS 5 1 Overload Protection 7 5 2 Over Temperature Protection 7 5 3 Low and High Voltage Protection 7 6 INSTALLATION INSTRUCTIONS 6 1 Inverter Mounting 8 6 2 Wiring 8 7 START UP PROCEDURE 9 8 SHUT OFF PROCEDURE 9 9 PRECAUTIONS 9 10 MAINTENANCE 9 11 SAFETY INSTRUCTIONS 10 12 TECHNICAL SPECIFICATIONS 11 13 SERVICE CODES 11 14 WARRANTY 12 ...

Page 3: ...oes not work Start up and shutdown is possible through any PROFESSIONAL SOLENER CONTROLLER using an optional control line In addition since the beginning of 2010 almost all versions feature a relay for generator start which is activated closing a potential free contact when the battery needs recharging This relay can be configured to perform other functions see some of these possible functions in ...

Page 4: ... These element references will be used throughout this manual The small model has one multi color LED that brings together the functions of the seven LED present in rest of the models 1 Alphanumeric Screen 2 Acoustic Alarm 3 Load Disconnection Indicator 4 Shortcircuit Indicator 5 Battery Over Voltage Indicator 6 Battery Under Voltage Indicator 7 Over Temperature Indicator 8 Load Detection Indicato...

Page 5: ...When the inverter DC voltage input drops to a value lower than the re start voltage setting the inverter will re start automatically Inverters produce heat when operating The amount of heat produced is almost proportional to the amount of power supplied by the inverter When the MOSFET reaches a certain programmed temperature 50 ºC by default the internal fan is activated stopping when the temperat...

Page 6: ...attery input voltage and turns off when it drops to a safe operating voltage value Overload Red It flashes when a short circuit takes place It remains lit if it exceeds the overload preset time Load Disconnection Red It turns ON when the inverter has shut off AC output disconnected to protect the installation or the inverter itself The yellow or red LED that remains lit together with the Load Disc...

Page 7: ...s the difference in form of heat particularly when the unit is operating close to its nominal power capacity When the inverter is subject to a heavy load for a prolonged period of time the overheating protection will be triggered in three stages first activating its internal fan then if the temperature keeps increasing it reduces the output voltage by 10 and if temperature continues rising it cuts...

Page 8: ...e or with a red terminal to connect to the positive terminal of the battery A black or blue cable to connect to the negative terminal of the battery A three wire cable phase neutral and ground or an industrial connector for connection to the AC loads An optional two wire cable to connect to the remote control Battery cables have a terminal at the end which must be attached with bolts to the termin...

Page 9: ...hat adjusted with the load detection potentiometer the inverter will start and the output voltage will increase rapidly until it reaches its nominal value If not load will turn ON and OFF once per second Verify that the RCD is working properly by pressing the test button on the front if it trips then it is working properly This cross check must be done occasionally as indicated by the manufacturer...

Page 10: ...e battery correctly Overload or short circuit Load Disconnection and Shortcircuit if applicable LED alarms will turn on Turn OFF the inverter eliminate the cause of shortcircuit or overload and turn on the inverter again High Battery voltage Load Disconnection and High Battery Voltage LED alarms turn on Inverter automatically restarts beware when battery voltage drops to reconnection voltage Low B...

Page 11: ...gth mm 115 315 315 315 460 460 460 535 535 535 647 Height mm 230 118 118 118 157 157 157 178 178 178 210 Width mm 154 192 192 192 255 255 255 285 285 285 344 Net Weight kg 4 9 9 12 20 22 22 24 36 36 68 Relay see Section 1 NO NO NO NO NO YES YES YES YES YES YES PROTECTIONS Against Reverse Polarity using intelligent diode Against High and Low Voltage Against Shortcircuit and Overload Against Over Te...

Page 12: ... examine and test the product according to prevailing rates The warranty is solely limited to the repair materials and labor of the equipment in no case includes travel expenses freight or shipping costs or any damage caused by the use of or inability to use the equipment The use of our products in life support devices without the express written permission of our company President is specifically...

Reviews: