6. COMMUNICATION
INTERFACE:
The UPS provides both computer interfaces, smart software (RS-232) and dry
contact (DB-9); by using different software and cable, the UPS shows different
monitoring function.
6.1
The definition and setup for RS-232 is as following:
Baud Rate : 2400 dps
Data Length : 8 bits
Stop Bit
: 1 bit
Parity :
None
Pin #6
: RS-232 data Tx out.
Pin #7
: Common of Pin #6 and Pin #9
Pin #9
: RS-232 data Rx In
6.2
The definition and setup for DB9 (optional) is as following:
Pin #2
: AC Power Failure
Pin #4
: Common GND of Pin #2 & Pin #5
Pin #5
: UPS Battery Low
Pin #6
: Turn off UPS
Pin #7
: GND of Pin6
The interface with computer is diagramed as above for your reference. Use Pin #4 as the
common of Pin #2 and Pin #5, Pin #2 and Pin #4 will become close loop from open when
the utility fails, Pin #5 and Pin #4 will become close loop from open when the battery level
is low.
The UPS will shut down itself when the high level signal from RS-232, sustained for
3 seconds, is applied between Pin #6 and Pin #7.
5 4 3 2 1
9 8 7 6