8.1.1 LEDs
The inverter is equipped with two LED indicators “white” and “red” which
provide information about the various operating states.
LED A:
The LED A is lit when the inverter is operating normally. The LED A is off The
inverter is not feeding into the grid.
The inverter is equipped with a dynamic power display via the LED A.
Depending on the power, the LED A pulses fast or slow.If the power is less
than 45% of power,the LED A pulses slow.If the power is greater than 45% of
power and less than 90% of power ,the LED A pulses fast.The LED A is
glowing when the inverter is in Feed-in operation with a power of at least 90%
of power.
LED B:
The LED B flashes during communication with other devices e.g.
AiCom/AiManager, Solarlog etc. Also, the LED B flashes during firmware
update through RS485.
LED C:
The LED C is lit when the inverter has stopped feeding power into the grid due
to a fault. The corresponding error code will be shown on the display.