36 UM0012_ASW 5-10k Series_EN_V03_0522
The active power limit can be set on “AiSWEI APP” application, the details can be
found in the user manual for the AISWEI APP.
6.3 Inverter demand response modes (DRED)
The inverter shall detect and initiate a response to all supported demand
response commands , demand response modes are described as follows:
Mode
Requirement
DRM 0
Operate the disconnection device
DRM 1
Do not consume power
DRM 2
Do not consume at more than 50% of rated power
DRM 3
Do not consume at more than 75% of rated power AND Source
reactive power if capable
DRM 4
Increase power consumption (subject to constraints from other
active DRMs)
DRM 5
Do not generate power
DRM 6
Do not generate at more than 50% of rated power
DRM 7
Do not generate at more than 75% of rated power AND Sink
reactive power if capable
DRM 8
Increase power generation (subject to constraints from other
active DRMs)
DRMS application description
• Only applicable to AS/NZS4777.2:2020.
• DRM0, DRM5, DRM6, DRM7, DRM8 are available.