User Manual UM0016_ASW 25K-40K-LT-G3_EN_V02_0622 43
The inverter shall detect and initiate a response to all supported
demand response commands, demand response modes are
described as follows:
Mode
Requirement
DRM 0 Operate the disconnection device
DRM 1 Do not consume power
DRM 2 Do not consume at more than 50% of rated power
DRM 3
Do not consume at more than 75% of rated power
AND Source reactive power if capable
DRM 4
Increase power consumption (subject to constraints
from other active DRMs)
DRM 5 Do not generate power
DRM 6 Do not generate at more than 50% of rated power
DRM 7
Do not generate at more than 75% of rated power
AND Sink reactive power if capable
DRM 8
Increase power generation (subject to constraints
from other active DRMs)
If DRMs support is required, the inverter should be used in
conjunction with AiCom. the Demand Response Enabling Device
(DRED) can be conneted to the DRED port on AiCom via RS485
cable. You can vist the website www.solplanet.net for more
information and download the user manual for the AiCom.
6.5 Communication with the third party device
Solplanet inverters can also connect with one third party device
instead of RS485 or WiFi stick, the communication protocol is
modbus. For more information, please contact the Service.