16 User Manual UM0007_ASW3000-5000H-S_EN_V01_0321
protective roof. Do not completely cover the top of the
inverter.
4. The mounting condition must be suitable for the weight and
size of the inverter. The inverter is suitable to be mounted on
solid wall that is vertical or tilted backwards (Max. 15°). It is
not recommended to install the inverter on the wall made of
plasterboards or similar materials. The inverter may make
noise when working.
5. To ensure adequate heat dissipation, the clearances between
the inverter and other objects are recommended as follows:
Clearances for one inverter
Direction Min. clearance (mm)
above
500
below
500
sides
300