19
parameter
default
desciption
MP
P
T
Constant
valu
e
Fi
x speed
Const.
valu
e 2 set
Fi
x speed 2 val.
External
speed
1
delay time with which the pumps
DOL start after the variable speed
pump has reached the maximum
frequency and the readen value has
fallen below set value
–
delta
control.
9
9
OFF
Function to enable multiple VASCO
Solar
’s to work in parallel as
described in the technical appendix
(see the relevant chapter). Up to 8
VASCO Solar units can be connected
in parallel.
VASCO Solar
’s communication
through RS 485 gates is granted by a
private protocol.
9
9
Direc
t
Direct: increasing measured value,
VASCO Solar decreases motor
frequency.
Reverse: increasing measured value,
VASCO Solar increase motor
frequency.
9
9
--->
If, during the test, the motor runs in
reverse, it is possible to change the
wiring sequence via software
without physically changing wires at
the terminals.
9
9
9
9
9
9
0.65
If the pump goes into dry-running,
the cosphi reaches its lowest level.
To set this value, contact the pump
manufacturer or test by closing the
suction and checking the value on
the VASCO Solar display; a value can
be set by assuming a dry cosphi
equivalent to 60% of the rated
cosphi specified by the
manufacturer.
9
9
9
9
9
9
10
Restart delay after a dry running
alarm. At each tentative (max 5)
restart delay will be doubled.
9
9
9
9
9
9
N.O.
By selecting N.A. (normally open)
VASCO Solar runs the motor if the
digital input 1 is open; motor will
be stopped if the digital input 1 is
closed.
By selecting N.C. (normally closed)
VASCO Solar runs the motor if the
digital input 1 is closed; motor will
be stopped if the digital input 1 is
opened.
9
9
9
9
9
9
N.O.
By selecting N.A. (normally open)
VASCO Solar runs the motor if the
digital input 2 is open; motor will
be stopped if the digital input 2 is
closed.
9
9
9
9
9
9
Digital input 2
N.O. / N.C.
Digital input 1
N.O. / N.C
.
Restarts delay
t = XX [min]
Dry run cosphi
cosphi = X.XX
Rotation sense
---> / <---
PI control
Direct/Reverse
COMBO
ON/OFF
Start delay AUX
t = XX [s]