Rated output power
7.6kW
6kW
Max. apparent output power
12.2 kVA, 10 sec
9.6 kVA, 10 sec
AC Output (Backup and Off-grid)
Max. output current for 10 seconds
PV Max. efficiency
PV CEC efficiency
BAT charged by PV Max. efficiency
BAT charged/discharged to AC Max. efficiency
97.6%
97.2%
98.5%
97.0%
Rated AC output current (continuous)
25A
40A
Max. allowable phase imbalance
Backup support configurations
Power Factor
THDv(@linear load)
100%
Dedicated loads and whole-home (with a Solis Power Hub)
>
0.99 (0.8 leading - 0.8 lagging)
<3%
Efficiency
Protection
Ground fault detection
Residual (leakage) current detection
Integrated AFCI (DC arc-fault circuit protection)
DC reverse-polarity protection
Rapid Shutdown NEC 2017
Compatible RSD Receivers
Protection class/Over voltage category
Yes (PV only)
Integrated SunSpec-certified Transmitter
See MLRSD compatibility sheet
I/II
Rated grid frequency
Max. output current for 300 milliseconds
60 Hz
Rated output voltage(L1-L2)/(L1/L2-N)
AC output voltage range
240 V/120 V
204-276 V
Back-up switch time
Phase Power
<
10 ms
240V Split-Phase
31.7A
50.7A
Yes
Yes
Yes
Technical Data
S6-EH1P6K-H-US
S6-EH1P7.6K-H-S-US
42
7. Specifications
45A
57.06A