Visibility of the LED status indicator lights and the LCD located at the front panel of
the inverter should be considered.
Adequate ventilation must be provided if the inverter is to be installed in a confined space.
NOTE:
Nothing should be stored on or placed against the inverter.
12in
2
0
in
2
0
in
12in
12in
1
2
in
1
2
in
Figure 4.2 Inverter Mounting Clearance
4. Installation
4. Installation
Dimensions of mounting bracket:
Figure 4.4 Inverter Wall Mounting
Please see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter to a wall or pillar.
Figure 4.3 Inverter Wall Mounting
.10.
.11.
4.2 Mounting the Inverter
The inverter shall be mounted vertically. The steps to mount the inverter are listed below:
1. According to the figure 4.2, select the mounting height of the bracket and mark the
mounting holes. For brick walls, the position of the holes should be suitable for the
expansion bolts.
Locking screw
Suitable fixing screws
Bracket
When one or more inverters are installed in one location, a minimum of 12
inches of
clearance should be kept between each inverter or other objects. The bottom of the
inverter should have 20 inches of clearance to the ground.
Install vertically with a maximum incline of +/- 5
°.
If the mounted inverter is tilted to an
angle greater than the maximum noted, heat dissipation will be inhibited, and may result
in power limiting.