6. Operation
6. Operation
.38.
.39.
Figure 6.25 Volt-VAR
Voltage1
:
210V
Voltage2
:
236V
Default Settings for UL1741SA:
Q1: (0-60%) D30% Q4: (-60%-0%) Default -30%
Rated 240V Grid
V1:(192-240V) Default 210V V2: (192-240V) Default 236V
V3:(240-288V) Default 243V V4: (240-288V) Default 264V
Rated 208V Grid
V1:(166-208V) Default 182V V2: (166-208V) Default 205V
V3:(208-240V) Default 211V V4: (208-240V) Default 229V
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1
YES=<ENT> NO=<ESC>
Power
Factor
:
+
1
.
00
Figure 6.27 PF Range
0,6
0,6
1,0
-1,0
P/P
n
under-excited
Q/P
n
under-excited
over-excited
over-excited
I
II
IV
III
-0,2
5. Reac-Power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
Figure 6.26 Fixed-PF
6. P-Factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
7.VgWatt-UL
Description: Inverter will change the active output power based on voltage change.
Note: This is the Volt-Watt Setting for UL1741SA Standards.
100
%
of
Input
Power
Vmin
Vnom
Vstart
Vstop
Vmax
AC Volt
0
Figure 6.28 Volt
-
Watt
characteristic
Figure 6.29 Vgwatt-UL
Voltage1
:
210V
Voltage2
:
236V
Default Settings for UL1741SA:
Rated 240V Grid
V1:less than V2
V2:less than Vstart
V3 (Vstart): (240-288V) Default264V
V4 (Vstop): (264-312V) Default 288V
P1:100% P2:100% P3: 100% P4:0%
Rated 208V Grid
V1:less than V2
V2:less than Vstart
V3 (Vstart): (208-250V) Default229V
V4 (Vstop): (229-270V) Default 250V
P1:100% P2:100% P3: 100% P4:0%