Malfunction display section 

When malfunction or protection occurs in the air conditioner, the indicators on outdoor main PCB will 

blink ( for detail, see "Display  and Meaning of Outdoor Indicator". When protection or malfunction  is

eliminated, display will be back to normal 

Sensor Malfunction

Handling method:

Check if the corresponding resistance of sensors( thermal resistor ) is normal ; plug well; the lead wire is not damage,

otherwise it is the sensor circuit or controller malfunction.

You can judge whether the sensor resistance is normal by measure the resistance or voltage and compare it with the 
corresponding sensor resistance or voltage table 

Overcurrent Protection

Possible reasons: the input voltage descend suddenly or the system overload.

Communicate Malfunction

Handling method:
Check if the communicate signal wire( indoor and outdoor connecting wire) is connected correctly and reliably.

System Abnormal

i.e. overload protection. When tube temperature (Check the temperature of outdoor heat exchanger  when cooling and 

check the temperature of indoor heat exchanger when heating) is too high,protection will be activated.
Possible reasons: the outdoor ambient temperature is too high when cooling, insufficient outdoor air circulation; and the
refrigerant flow malfunction. 

Compressor Overload Protection

Possible reasons: the refrigerant is not enough or is too much; the capillary is blocked and the temperature rises; the

compressor does not run smoothly(seized or jammed); exhaust valve is breakage; the protector itself has malfunction. 

(for detail, see " Compressor too hot, the stop often occur")

Handling method: adjust refrigerant amount; replace the capillary; replace the compressor; use the multimeter to check

whether the contactor of the compressor is fine when it is not overheated, if not, then replace the protector. 

Exhaust Protection

Possible reasons: 1. exhaust sensor does not connect well; 2.exhaust sensor resistance is abnormal; 3.sensor circuit

malfunction;4.cooling system malfunction: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short 

pass for condenser; the system has noncondensing gas (such as air, water etc.); blockage of capillary assy (including
filter); leakage inside four-way valve causes incorrect operation; malfunction of compressor; malfunction of protection
relay; malfunction of discharge sensor; outdoor temperature too high.

Handling method:1.re-plugging the exhaust sensor; 2.replace the exhaust sensor ; 3. replace the circuit  board; 4.repair 

system .

Summary of Contents for KFHHP-18

Page 1: ...1 208 V 230V R410A Introduction and Features Model Remarks SOLEUSAIR KFHHP 18...

Page 2: ...L Model KFHHP 18 Function Rated Voltage 208 V 230V Frequency Hz High Standard 60HZ Total Capacity W High Standard Total Capacity Btu h High Standard Nominal Power W Max Input W Rated Current A Air Fl...

Page 3: ...Discharge Permissible Excessive Operating Sound Pressure Level dB A H M L Dimension W D H in Dimension of Package W D H in Net Weight Gross Weight lb Refrigerant Charge oz Length ft Gas additional ch...

Page 4: ...Ubqf Sfdfjwjoh xjoepx Hvjef mpvwfs Bjs Pvumfu Bjs Jomfu MFE Cpbse Esbjobhf iptf Ajs jomfu GspouQbofm Xjsfmftt sfnpuf dpouspm Dpoofdujpo qjqf boe dpoofdujpo xjsf Bjs Pvumfu Component Name Indoor unit O...

Page 5: ...et Xbmm Qjqf Xsbqqjoh Ubqf Sfdfjwjoh xjoepx Hvjef mpvwfs MFE Cpbse Esbjobhf iptf Ajs jomfu GspouQbofm Air inlet Xjsfmftt sfnpuf dpouspm Dpoofdujpo qjqf boe dpoofdujpo xjsf Bjs Pvumfu Outdoor Unit Indo...

Page 6: ...4 Overall and Installing Dimension Overall and Installing Dimension of Indoor Unit Air inlet grill Left Tube exit hole Top View Right Tube exit hole Rear View rear panel Unit mm SOLEUSAIR...

Page 7: ...Overall and Installing Dimension of Outdoor Unit Unit mm Bolt Nut Wrench Comforstar Plus...

Page 8: ...Electrical Diagram 5 INCASE In case of any chang in the electrical diagram shown above please follow the drawing on the cabinet...

Page 9: ...oor room temp reach the preset temp rapidly and keep at preset temp Remote control signal and manual key signal manage Indoor fan high med low Swing step motor Indicator Buzzer Timer Sleep Memory Heat...

Page 10: ...essor frequency and outdoor fan speed automatically according to the demand of heating capacity to make the indoor temperature reach the preset temp rapidly When the heating capcity meet the demand th...

Page 11: ...r off according to the timer set by the remote controller MemoryFunction Contents of memory Mode Set fan speed Set temperature Swing If the system is de energized under timer or sleep function when re...

Page 12: ...attheexhausttemperaturehasresumednormal thecompressorwillresumerunning Ifitisdetectedthattheexhausttemperatureprotectionoccurs6timescontinuouslywithin1hour thecompressorcannotresumerunning inwhichcase...

Page 13: ...ing max cooling heating middlecooling heating min cooling heating switchoff lowpressurecannotresume blink1time blink1time blink blink1time bright LED4 LED5 LED6 LED7 LED8 blink2times blink2times blink...

Page 14: ...el you can use panel support bar to support the panel Screw off the fixing screws of the electric box cover and open the electric box top cover to take it off As shown in Fig 7 1 Panel panel sup port...

Page 15: ...assembling the electric box cover Unloose the 3 clasps to take off the electric box cover As shown in Fig 7 5 cl Fig 7 5 Fig 7 6 Fig 7 7 Disassembling the water tray assy Unloose the clasp on the left...

Page 16: ...p As shown in Fig 7 11 Screw off the fixing nut that fixes the cross flow fan to pull out the motor from the cross flow fan As shown in Fig 7 12 Disassembling the cross flow fan Refer to the above ste...

Page 17: ...ide plate refer to Figure7 13 Fig 7 13 Screw front side plate Disassemble Top Cover Unscrew the tapping screws fixing the top cover then pull upward and remove the top cover refer to Figure 7 14 top c...

Page 18: ...e screwdriver to screw off the two screws fixing the electric box and pull upward to remove the electric box refer to Figure 7 17 7 18 Screw Electric Box cover Screw Screw Right Side Plate Disassemble...

Page 19: ...or support and pull the motor support upward to remove it refer to Figure 7 21 Figure 7 21 the Motor Figure 7 20 Disassemble 4 Way Valve cooling only unit has not 4 way valve 4 Way Valve Soldering Scr...

Page 20: ...gas return pipe to take off big valve Note When soldering the soldered dot wrap big valve completely by moist cloth to prevent valve from damaging by high temperature Screw out the 2 bolts that fixing...

Page 21: ...8 Exploded View and Components and Parts List Exploded View of Indoor Unit SOLEUSAIR...

Page 22: ...aporator Support 1 28 Drainage Pipe 1 29 Pipe Clamp 1 30 Screw Cover 3 31 Fan Bearing 1 32 Motor FN20C PG 1 32 Motor FN21R 1 32 Motor FN21X 1 33 Swing Link 1 1 34 Swing Link 2 1 35 Swing Louver 11 36...

Page 23: ...Exploded View of Indoor Unit SOLEUSAIR...

Page 24: ...Exploded View of Outdoor Unit SOLEUSAIR...

Page 25: ...Support 1 34 Radiator 1 35 Power Module 1 36 Rectifler S25VB60 1 37 Metal Base 1 38 Handle 1 39 Front Side Plate 1 01233011 24213028 49013003 01303076 322100692 46010602 01203393 26235253 NONE 0010052...

Page 26: ...alfunction of remote controller Loose or poor connection of receiving head Receiving head is broken Measure the insulating resistance for grounding to confirm whether there is electrical leakage or sh...

Page 27: ...both thick pipe and thin pipe are insulated well The exposed part of the connector and copper pipe must be insulated as well Heat exchanger of outdoor unit is blocked Air filters are blocked Fan spee...

Page 28: ...control board and module Abnormal input of power module Abnormal output of power module Compressor temperature is too high Wrong wiring Damage of outdoor main control board Check the circuit according...

Page 29: ...ound inside four way valve when heating outer case Take out the foreign substance Adjust support washer of the compressor and Separate the touched pipeline tighten loose bolts Tighten connecting screw...

Page 30: ...system blockage the frost on the capillary don t melt Replace blockage component Check if the power supply circuit for motor on the controller is normal or replace the motor The power is abnormal Add...

Page 31: ...outdoor ambient temperature is too high when cooling insufficient outdoor air circulation and the refrigerant flow malfunction Compressor Overload Protection Possible reasons the refrigerant is not en...

Page 32: ...ure the voltage of outdoor fan connector No voltage Normal voltage Replace the fan Replacethemainboard motor of outdoor unit Check if radiating paste is spread evenly or radiating sticker is stuck wel...