Operating Procedures / Photos
Disassemble Capillary
Unsold the soldering points at the capillary, the
valve and the condenser to remove the capillary.
Pay attention not to allow the soldering slag to
block the capillary.
˄
refer to Figure
7
-23
˅
Capillar
y
Figure
7
-23
Disassemble Valve
s
Screw out the 2 bolts that fixing big valve,
unsolder the soldered dot connecting big valve with
gas return pipe to take off big valve.
(Note: When soldering the soldered dot, wrap big
valve completely by moist cloth to prevent valve
from damaging by h
igh
temperature.)
Screw out the 2 bolts that fixing small valve,
unsolder the soldered dot that connected small
valve and Y-shape pipe to take off small valve.
˄
refer to Figure
7
-2
4
˅
Figure
7
-2
4
big valve
bolts
small valve
Figure
7
-2
5
Disassemble Compressor
Unsolder the pipeline that connected with compres-
sor first,then take off the 3 nuts on feet of compres-
sor to take offcompressor.
Foot Nut
Compressor
˄
refer to Figure
7
-2
5
˅