ENGLISH
COMPACT WALL AND DUCT AXIAL FANS
The COMPACT Wall and Duct Axial fan series has been manufactured in accordance with the rigorous standards
of production as defined by the International Quality Standards ISO 9001. All components have been checked and
tested at the end of the manufacturing process.
We recommend that you check the following when receiving this product:
1. Correct size has been received.
2. Correct model has been received.
3. Details on the rating label correspond to the electrical supply; i.e. Voltage, frequency, etc.
Remove the unit from the packaging and inspect for shipping damage within 15 days of receipt. If the product is found
to be damaged, immediately contact your local authorized supplier. DO NOT OPERATE THIS UNIT IF DAMAGED.
These instructions should be considered as a supplement to EPA standard practices, as well as state and local
building code regulations.
ENVIRONMENT
The COMPACT Wall and Duct Axial series are suitable for exhaust or supply air operations in the temperature range
(inclusive if airstream temperature) of -40°C (-40°F) up to +60°C (140°F).
INSTALLATION
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have any questions contact the
manufacturer.
b) Before servicing or cleaning the unit, switch the power off at the service panel and lock the service
disconnecting means to prevent power from being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning device such as a tag to the service panel.
c) Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable
codes & standards including fire rated construction.
d) Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent back drafting. Follow the heating equipment manufacturers guideline and safety
standards such as those published by the National Fire Protection Association (NFPA) and the American
Society For Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities.
e) When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
f) Ducted fans must always be vented to the outdoors.
g) If this unit is to be installed over a tub or a shower, it must be marked as appropriate for the application and
connected to a GFCI (Ground Fault Circuit Interrupter) – protected branch circuit.
h) Never place a switch where it can be reached from a tub or shower.
i) Do not use this fan with any solid-state speed control device.
j)
CAUTION:
For General Ventilating Use Only. Do Not Use To Exhaust Hazardous Or Explosive Materials And
Vapors.
k)
CAUTION:
This unit has an unguarded impeller. Do Not Use In Locations Readily Accessible To People Or
Animals.
INSTALLATION OF COMPACT WALL AXIAL FANS.
See
Figure (1)
, in accordance with the information below.
Provide a secure structure to mount the fan. Additional structural members may be required to support the fan at
the fixing points. If the fan is to be mounted lower than the height recommended by local/national safety regulations
(normally 7 ft. minimum), an exhaust guard should be fitted. Please contact you local distributor for suitable
accessories.
4