4- COMMISSIONING
4.1- During installation:
The control panel allows you to adjust the installation settings, and lets you see the different operational
settings.
Down button
Display
screen
Up button
Confirm
button
MENU
OPTIONS
VALUES
FACTORY
SETTINGS
Language
English, Francais, Español, Deutsch,
Italiano, Nederlands
English
INSTALLATION SETTINGS
Dry contact
NO/NC
NO
Preheating Bat.
Yes/no
No
Postheating Bat.
Yes/no
No
Air quality sensor
Yes/no
No
Connection type
A / B
A
Units
m
3
/h / l/s
m
3
/h
Thermal delay
-
15%,…+15%
0
Air flow rate
- LS flow
60,…210 m
3
/h
60 m
3
/h
- HS flow / 1/2 hour boost
60,…210 m
3
/h
120 m
3
/h
- Free cooling 8H
60,…210 m
3
/h
210 m
3
/h
Air quality sensor adjustments
Minimum flow air quality sensor 0-10V
60,…210 m
3
/h
60 m
3
/h
Maximum flow air quality sensor 0-10V
60,…210 m
3
/h
120 m
3
/h
Minimum power air quality sensor 0-10V
0-10V
0
Maximum power air quality sensor 0-10V
0-10V
10
Automatic bypass
On/Off
On
Automatic outdoor temp. bypass
11,…20ºC
+ 12ºC
Automatic indoor temp. bypass
21,…30ºC
+ 24ºC
Manual bypass settings
1,…24 Hours
8 H
Type of defrost
Slow Induction / Stop Induction
Preheating Battery
- Temperature to turn ON the battery
-
15,…5ºC
0ºC
- Temperature to turn OFF the battery
-
5,…10ºC
+ 5ºC
- Constant temperature
+1,…10ºC
+ 4ºC
Postheating Battery
Constant temperature
12,…30ºC
+ 18ºC
Reset to factory settings
Yes/no
No
CONSULTING STATUS SETTINGS
Current flow
60,…210
Defrost
On, Off
Batteries
PREheating: On/Off - POSTheating: On,
Off
Software version
V0.0
Extractor fan motor
Error, Ok
Induction fan motor
Error, Ok
Bypass
Error, Ok
Remote control connection
Error, Ok
Sensors
Error, Ok Temp. Extraction, Extracted,
Intake, Induction
Extraction temp.
Extracted air temp.
Air intake temp.
Induction temp.
Off