24
Minimum airflow air quality sensor*:
Setting the minimum airflow.
Use the button and choose the minimum airflow
with buttons
,
then confirm with the
button.
Maximum airflow air quality sensor*:
Setting the maximum airflow.
Use the button and choose the minimum airflow
with buttons
,
then confirm with the
button.
Minimum power air quality sensor*:
Setting the minimum power.
Use the
button and choose the power with
buttons
,
then confirm with the
button.
Maximum power air quality sensor*:
Setting the maximum power.
Use the
button and choose the power with
buttons
,
then confirm with the
button.
Qmin.
Qmax.
Umin.
Umax.
Flow (m
3
/h)
Power (v)
Diagram showing the
air quality sensor (0-10V)*
*: Humidity probe, CO2, COV.
Automatic bypass:
You can enable or disable the automatic bypass.
Use the button and activate (ON) or deactivate (OFF) with the
buttons, then
confirm with the button.
On having avoided the heat exchanger, the 100% by-pass system of the
FLEXEO allows the introduction of fresh air in the night without being warmed by
the warm air accumulated in the house during the day.
This system works automatically with this conditions:
-Tº inner >1+ Tº outer and Tº inner > +24ºC and Tº outer> +12ºC,
If the function is disabled, You can manually switch to by-pass, by pressing the by-pass
button. During this operation it is possible to cancel this function by pressing the by-pass
key once more.
Automatic outdoor temp. bypass:
You can change the outside temperature that activates the bypass.
Factory settings = +12ºC
Temperature range: +11
–
+20ºC
Use the button and change the temperature with the
buttons, then confirm
with the button.
Automatic indoor temp. bypass:
You can change the indoor temperature that activates the bypass.
Factory settings = +24ºC
Temperature range: +21
–
+30ºC
Use the button and change the temperature with the
buttons, then confirm with the
button.
Manual bypass settings:
You can manually change the running time of the bypass.
Factory settings = 8 hours
Time range: 1
–
24 hours
Use the button and change the running time with the
buttons, then confirm with the
button.