37
PVI 3800TL
Percentage of voltage loss with 208 V AC and 240 V AC service. The load used in the calculation
is the max. continuous AC current of the inverter.
2.0%
1.6%
1.2%
0.8%
0.4%
0.0%
20
40
60
80
100
120
140
One way distance in feet
Percent of voltage loss
10
AWG
8
AWG
6
AWG
Figure 33: PVI 3800TL-AC voltage loss with different wire sizes and lengths
PVI 7600TL
Percentage of voltage loss with 208 V AC and 240 V AC service. The load used in the calculation
is the max. continuous AC current of the inverter.
2.0%
1.6%
1.2%
0.8%
0.4%
0.0%
20
40
60
80
100
120
140
One way distance in feet
Percent of voltage loss
8
AWG
6
AWG
Figure 34: PVI 7600TL- AC voltage loss with different wire sizes and lengths
10
A
WG